M800/M80/E80 Series Maintenance Manual
4 Failure Diagnosis
89
IB-1501273-F
(*1) As for the NC unit, the contents are as follows depending on the condition:
NC
Communication between NC unit and display unit
Item
Details
Battery vol state
This displays the current state of the battery voltage as 0 or 1.
Condition
Class
0 (normal state)
-
1 (encoder error)
(no battery)
Warning (yellow)
Battery used years
This displays approximate time of the battery used from the last replacement.
Condition
Class
Recommended battery use (5 years) <= Time for the bat-
tery used
Warning (yellow)
NC : temp. 1 (°C)
This displays the current temperature of the control unit.
Condition (M800S: Main card /M80/E80)
Class
78.5°C < Control unit temp. <= 81°C
Caution (gray)
81°C < Control unit temp.
Warning (yellow)
Condition (M800W: Main card)
Class
79°C < Control unit temp. <= 84.5°C
Caution (gray)
84.5°C < Control unit temp.
Warning (yellow)
Condition (M80W: Main card)
Class
79°C < Control unit temp. <= 81.5°C
Caution (gray)
81.5°C < Control unit temp.
Warning (yellow)
Fan rev (r/min)
This displays the current fan rotation speed of the control unit.
Condition
Class
Fan rot. speed <= 4000 r/min
Warning (yellow)
Item
Details
Servo comm err Num1
This displays the count of occurrence for "Y51 SV commu er: Recv frame No. xx04"
after the power ON.
Servo comm err Acc1
This displays the cumulated count of occurrence for " Y51 SV commu er: Recv
frame xx04".
Press the menu [Servo clear] to clear the cumulated count to "0".
Servo comm err Num2
This displays the count of occurrence for "Y51 SV commu er: Data ID error xx03"
after the power ON.
Servo comm err Acc2
This displays the cumulated count of occurrence for "Y51 SV commu er: Data ID er-
ror xx03".
Press the menu [Servo clear] to clear the cumulated count to "0".
RIO channel/station1
This displays the Channel No./Station No. of occurrence for continuous error after
the power ON.
RIO retry count max 1
This displays the maximum value of the continuous error after the power ON.
RIO channel/station 2
This displays the Channel No./Station No. held even if the power OFF.
Press the menu [RIO clear] to clear the Channel No./Station No. to "0/0".
RIO retry count max 2
This displays the count held even if the power OFF.
Press the menu [RIO clear] to clear the count to "0".
Ether comm err Num
This displays the number of Ethernet communication error after PLC program is ex-
ecuted once.
Ether comm err Acc
This displays the cumulated count of occurrence for Ethernet communication error.
Press the menu [Ether clear] to clear the cumulated count to "0".
Overvoltage Acc
This displays the cumulated count of detection frequency of overvoltage after the
power ON.
Press the menu [Cl. ov.history] to clear the cumulated count to "0".
Power losses Num
This displays the count of detection frequency of instantaneous power interruption
after the power ON.
Содержание E80 Series
Страница 1: ......
Страница 7: ......
Страница 17: ......
Страница 19: ......
Страница 21: ......
Страница 23: ......
Страница 25: ......
Страница 28: ...1 1 IB 1501273 F System Basic Configuration ...
Страница 68: ...2 41 IB 1501273 F Daily Maintenance and Periodic Maintenance ...
Страница 78: ...3 51 IB 1501273 F Maintenance of the Drive Unit ...
Страница 101: ...M800 M80 E80 Series Maintenance Manual 3 Maintenance of the Drive Unit 74 IB 1501273 F ...
Страница 102: ...4 75 IB 1501273 F Failure Diagnosis ...
Страница 165: ...M800 M80 E80 Series Maintenance Manual 4 Failure Diagnosis 138 IB 1501273 F ...
Страница 166: ...5 139 IB 1501273 F Troubleshooting ...
Страница 169: ...M800 M80 E80 Series Maintenance Manual 5 Troubleshooting 142 IB 1501273 F ...
Страница 170: ...6 143 IB 1501273 F Replacing Each Unit ...
Страница 194: ...M800 M80 E80 Series Maintenance Manual 6 Replacing Each Unit 167 IB 1501273 F FCU8 DX651 Mounting screw size M5 ...
Страница 205: ...M800 M80 E80 Series Maintenance Manual 6 Replacing Each Unit 178 IB 1501273 F ...
Страница 212: ......