OPERATING PROCEDURE
PHOTOS/FIGURES
(6)
Remove 2 electrical parts box fixing screws (4 × 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Photo 5
4. Removing the thermistor <Suction pipe> (TH6)
(1)
Remove the service panel. (See Photo 1)
(2)
Remove the top panel. (See Photo 1)
(3)
Disconnect the connectors, TH6 and TH7 (red), on the
outdoor multi controller circuit board in the electrical parts
box.
(4)
Loosen the wire clamps on the side of the electrical parts
box, and next to it.
(5)
Pull out the thermistor <Suction pipe> (TH6) from the
sensor holder.
Note: When replacing thermistor <Suction pipe> (TH6),
replace it together with thermistor <Ambient> (TH7)
since they are combined together.
Refer to procedure No.5 below to remove thermistor
<
Ambient>
(TH7).
Photo 6
Photo 7
5. Removing the thermistor <Ambient> (TH7)
(1)
Remove the service panel. (See Photo 1)
(2)
Remove the top panel. (See Photo 1)
(3)
Disconnect the connector TH7 (red) on the outdoor multi
controller circuit board in the electrical parts box.
(4)
Loosen the wire clamps on top of the electrical parts box.
(See Photo 6)
(5)
Pull out the thermistor <Ambient> (TH7) from the sensor
holder.
Note: When replacing thermistor <Ambient> (TH7),
replace it together with thermistor <Suction pipe>
(TH6), since they are combined together.
Refer to procedure No.4 above to remove thermis
-
tor <Suction pipe> (TH6).
Photo 8
Electrical parts box
Hooks
Hook
Electrical parts
box fixing screws
Electrical
parts box
Clamps
Thermistor
<Suction pipe> (TH6)
Thermistor
<Compressor> (TH4)
Ball valve and
stop valve
fixing screws
Thermistor
<HIC pipe> (TH2)
Lead wire of thermistor <Ambient> (TH7)
Sensor holder
149
OCH673D
149