Check code
70
71
OCH673D
4-way valve trouble in heating mode
Abnormal points and detection methods
Causes and checkpoints
If 4-way valve does not operate during heating operation.
When any of the following temperature conditions is satisfied for 3 minutes
or more during heating operation
1. TH22j−TH21j
[
−10°C [−18°F]
2. TH23j−TH21j
[
−10°C [−18°F]
3. TH22j
[
3
_
C [37.4°F]
4. TH23j
[
3
_
C [37.4°F]
Note:
For indoor unit, the abnormality is detected if an operating unit satisfies the
condition.
4-way valve failure
Disconnection or failure of 4-way valve coil
Clogged drain pipe
Disconnection or loose connection of connectors
Malfunction of input circuit on outdoor multi controller circuit board
Defective outdoor power circuit board
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Is the connector for outdoor multi
controller circuit board or 4-way
valve coil disconnected or loose?
Reconnect the connector or connect it
tightly.
Yes
Disconnect the connector for outdoor multi
controller circuit board or 4-way valve coil
to check the resistance.
No
Replace the 4-way valve coil.
Replace the outdoor multi controller circuit
board.
Is the detected voltage normal?
Is it free from any trace of
over-heating or burning?
Is the resistance detected?
Check the voltage and appearance of the
outdoor multi controller circuit board.
No
No
Yes
1508
(EF)
Yes
Replace the 4-way valve.
Please refer to ''8-7. HOW TO
CHECK THE PARTS'' for ohm
values.
Содержание CITY MULTI
Страница 35: ...35 OCH673D PUMY P112YKME4 BS R2 PUMY P125YKME4 BS R2 PUMY P140YKME4 BS R2 ...
Страница 159: ...159 OCH673D ...