Check code
1302
(UE)
High pressure trouble
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 2 of 4
No
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Is the indoor unit filter clogged?
Clean the filter.
(Clogged filter)
(No clog)
Continued from the previous page.
Is there dirt on the indoor heat
exchanger?
Is the outdoor unit short-cycled?
Is there dirt on the outdoor heat
exchanger?
Are the pipes clogged or broken?
Wash the indoor heat exchanger.
Resolve the short cycle.
Wash the outdoor heat exchanger.
Check and repair piping.
(dirty)
(dirty)
(short-cycled)
(no dirt)
(no dirt)
(no short-cycle)
Continue to the next page.
Disconnect the TH7 wiring and check the
resistance.
61
OCH673D
Содержание CITY MULTI
Страница 35: ...35 OCH673D PUMY P112YKME4 BS R2 PUMY P125YKME4 BS R2 PUMY P140YKME4 BS R2 ...
Страница 159: ...159 OCH673D ...