ELECTRICAL WIRING
9-1. OVERVIEW OF POWER WIRING
9-2. WIRING OF MAIN POWER SUPPLY AND EQUIPMENT CAPACITY
9-2-1. Wiring diagram for main power supply
This chapter provides an introduction to electrical wiring for CITY MULTI series, together with notes concerning power wiring,
wiring for control (transmission wires and remote controller wires), and the frequency converter.
■ Schematic Drawing of Wiring: When NOT using a Branch Box (example)
PUMY-P•VKM4 series
PUMY-P•YKM(E)4 series
■ Schematic Drawing of Wiring: When using a Branch Box (example)
<When power is supplied from the outdoor unit>
PUMY-P•VKM4 series
B
C
3N
~
380-400-415 V, 50 Hz
~
/N
220-230-240
V, 50 Hz
~
/N 220 V, 60 Hz
3N
~
380 V, 60 Hz (YKM4 only)
L/N
A
A
L1/L2/L3/N
B
;
;
B1/B2
;
;
B1/B2
D
D
D
D
L/N
S1/S2/S3
S1/S2/S3
C
L/N
S1/S2/S3
S1/S2/S3
D
;
;
;
;
;
;
;
;
;
S1/S2/S3
S1/S2/S3
Note:
Reactor Box (optional parts PAC-RB01BC)
When the product is used for a purpose other
than as professional equipment,
the Reactor Box may be necessary.
Brach box power supply method
Outdoor unit
Power supply
from outdoor unit
Separate power
supply
1-phase power
supply
Unnecessary
Necessary
3-phase power
supply
Necessary
Necessary
(1) Use a separate power supply for the outdoor unit and indoor unit.
(2)
Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
(3)
The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.
(4) Specific wiring requirements should adhere to the wiring regulations of the region.
(5) Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord
(design 60245 IEC57). For example, use wiring such as YZW.
(6) Install an earth line longer than power cables.
Warning:
· Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not
fixed firmly, it may cause heating or fire.
· Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some
amount of direct current.
Caution:
· Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may
cause an electric shock.
· Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large
capacity may cause a malfunction of unit or fire.
· Be sure to install N-Line. Without N-Line, it could cause damage to the unit.
PUMY-P•YKM(E)4 series
~
/N 220-230-240 V, 50 Hz
~
/N 220 V, 60 Hz
L/N
A
B
A
E
L/N
E
L/N
E
L/N
E
L/N
F
;
;
;
;
;
~
/N 220-230-240 V, 50 Hz
~
/N 220 V, 60 Hz
3N
~
380-400-415 V, 50 Hz
L1/L2/L3/N
A
Switch (Breakers for Wiring and Current Leakage)
B
Outdoor Unit
C
Branch Box
D
A-Control Indoor Unit
E
M-NET Control Indoor unit
F
Pull Box
Note: The M-NET control indoor unit cannot receive power
supplied from an outdoor unit, so provide it with power
separately.
;
A
B
3N
~
380 V, 60 Hz (YKM4 only)
No.
SW1 setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678
1
2
3
4
5
6
7
8
220
001
1101
1
IC6 TH23
(Gas)
−99.9–999.9 (ºC)
Display detected data of indoor unit thermistor
221
101
1101
1
IC7 TH23
(Gas)
222
01111
011
IC8 TH23
(Gas)
223
11111
011
IC6 TH22
(liquid)
224
000001
11
IC7 TH22
(liquid)
225
100001
11
IC8 TH22(liquid)
226
010001
11
IC6
TH21 (intake)
227
110001
11
IC7
TH21 (intake)
228
001001
11
IC8
TH21 (intake)
229
101001
11
IC6 SC/SH
−99.9–999.9 (ºC)
during heating: subcool (SC)/during cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH data
230
01
1001
11
IC7 SC/SH
231
111
00
111
IC8 SC/SH
232
000101
11
Target indoor SC/SH
(IC6)
SCm/SHm (0.0–20.0) (ºC)
Display of all control target data
233
100101
11
Target indoor SC/SH
(IC7)
234
010101
11
Target indoor SC/SH
(IC8)
235
110101
11
IC6 LEV opening pulse
abnormality delay
0–2000 (pulse)
Display of opening pulse of indoor LEV at time of abnormality delay
236
001
101
11
IC7 LEV opening pulse
abnormality delay
237
101
101
11
IC8 LEV opening pulse
abnormality delay
238
0111
0111
IC6 SC/SH at time of abnormality delay
−99.9–999.9 (ºC)
During heating: subcool (SC) During cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH data at time of abnormality delay
239
1111
0111
IC7 SC/SH at time of abnormality delay
240
00001
11
1
IC8 SC/SH at time of abnormality delay
241
10001
11
1
IC6 LEV opening pulse
at time of abnormality
0–2000 (pulse)
Display of opening pulse of indoor LEV at time of abnormality
242
01001
11
1
IC7EV opening pulse at time of abnormality
243
11
00
1111
IC8 LEV opening pulse
at time of abnormality
244
00101
11
1
IC6 SC/SH at time of
abnormality
−99.9–999.9 (ºC)
During heating: subcool (SC) During cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH data at time of abnormality delay
245
10101
11
1
IC7 SC/SH at time of
abnormality
246
011
01111
IC8 SC/SH at time of
abnormality
250
01
011111
IC9 LEV opening pulse
0–2000 (pulse)
Display of opening pulse of indoor LEV
251
11
011111
IC10 LEV opening pulse
252
00
111111
IC1
1 LEV opening pulse
253
10
111111
IC12 LEV opening pulse