15
OCH673D
15
<Heating>
Design Condition
Outdoor Design Wet Bulb Temperature
2ºC
Total Heating Load
13.2 kW
Room1
Indoor Design Dry Bulb Temperature
23ºC
Heating Load
5.4 kW
Room2
Indoor Design Dry Bulb Temperature
23ºC
Heating Load
7.8 kW
<Other>
Indoor/Outdoor Equivalent Piping Length
60 m
Capacity of indoor unit
Unit: kW
P•FY series
Model Number
for indoor unit
Model 10 Model 15 Model 20 Model 25 Model 32 Model 40 Model 50 Model 63 Model 71 Model 80 Model 100 Model 125 Model 140
Model
Capacity
1.4
1.9
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
M series
S series
P series
Model Number
for indoor unit
Model 15 Model 18 Model 20 Model 22 Model 25 Model 35 Model 42 Model 50 Model 60 Model 71 Model 80 Model 100
Model
Capacity
1.7
2.1
2.3
2.5
2.9
4.0
4.8
5.7
6.9
8.1
9.3
11.2
2. Heating Calculation
(1) Temporary Selection of Indoor Units
Room1
PEFY-P50
6.3kW (Rated)
Room2
PEFY-P71
9.0kW (Rated)
(2) Total Indoor Units Capacity
P50 + P71 = P121
(3) Selection of Outdoor Unit
The P125 outdoor unit is selected as total indoor units capacity is P121
PUMY-P125
16.0 kW
(4) Total Indoor Units Capacity Correction Calculation
Room1
Indoor Design Dry Bulb Temperature Correction (23ºC) 0.88 (Refer to Figure 4)
Room2
Indoor Design Dry Bulb Temperature Correction (23ºC) 0.88 (Refer to Figure 4)
Total Indoor Units Capacity (CTi)
CTi = Σ (Indoor Unit Rating × Indoor Design Temperature Correction)
= 6.3 × 0.88 + 9.0 × 0.88
= 13.5 kW
(5) Outdoor Unit Correction Calculation
Outdoor Design Wet Bulb Temperature Correction (2ºC)
1.00 (Refer to Figure 5)
Piping Length Correction (60 m)
0.96 (Refer to Figure 6)
Defrost Correction
0.89 (Refer to Table 1)
Total Outdoor Unit Capacity (CTo)
CTo = Outdoor Unit Rating × Outdoor Design Temperature Correction × Piping Length
Correction × Defrost Correction
= 16.0 × 1.00 × 0.96 × 0.89
= 13.7 kW
(6) Determination of Maximum System Capacity
Comparison of Capacity between Total Indoor Units Capacity (CTi) and Total Outdoor Unit Capacity (CTo)
CTi = 13.5 < CTo = 13.7, thus, select CTi.
CTx = CTi = 13.5 kW
(7) Comparison with Essential Load
Against the essential load 13.2 kW, the maximum system capacity is 13.5 kW: Proper indoor units have been selected.
(8) Calculation of Maximum Indoor Unit Capacity of Each Room
CTx = CTo, thus, calculate by the calculation below
Room1
Indoor Unit Rating × Indoor Design Temperature Correction
= 6.3 × 0.88
= 5.5 kW
OK: fulfills the load 5.4 kW
Room2
Indoor Unit Rating × Indoor Design Temperature Correction
= 9.0× 0.88
= 7.9 kW
OK: fulfills the load 7.8 kW
Note: If CTx = CTo, please refer to the <Cooling> section to calculate the Maximum Indoor Unit Capacity of Each Room.
Completed selecting units since the selected units fulfill the heating loads of Room 1, 2.
15
16
17
18
19
20
21
22
23
24
25
26
27
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Ratio of heating capacity
Indoor Temperature [°CD.B.]
−20
−15
−10
−5
0
5
10
15
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Ratio of heating capacity
Outdoor Temperature [°C W.B.]
20°C D.B
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
20
0
40
60
80 100 120 140 160 180 200
Heating capacity correction factor
Piping equivalent length (m)
Figure 4
Indoor unit temperature correction
To be used to correct indoor unit only
Figure 5
Outdoor unit temperature correction
To be used to correct outdoor unit only
Figure 6
Correction of refrigerant piping length
Table 1 Table of correction factor at frost and defrost
Outdoor inlet air temp. °C 6
4
2
0 -2 -4 -6 -8 -10 -15 -20
PUMY-P112,125,140VKM4 1.0 0.98 0.89 0.88 0.89 0.90 0.95 0.95 0.95 0.95 0.95
PUMY-P112,125,140YKM(E)4
1.0 0.98 0.89 0.88 0.89 0.90 0.95 0.95 0.95 0.95 0.95
Содержание CITY MULTI
Страница 35: ...35 OCH673D PUMY P112YKME4 BS R2 PUMY P125YKME4 BS R2 PUMY P140YKME4 BS R2 ...
Страница 159: ...159 OCH673D ...