Check code
1102
(U2)
Compressor temperature trouble
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
*For the voltage, refer to "8-8.HOW TO
CHECK THE COMPONENTS".
Yes
Yes
Yes
No
No
No
Continued from the previous page.
Is the voltage normal value?
Is it free from any trace of over-
heating or burning?
Is the resistance detected?
Is the resistance detected?
Check the voltage(*) and appearance of
the outdoor multi controller circuit board.
Disconnect the thermistor wiring to check
the resistance.
Disconnect the indoor LEV wiring and
check the resistance.
Replace the outdoor multi controller circuit
board.
Replace the thermistor.
Replace the indoor LEV.
Replace the indoor controller board.
Chart 2 of 2
59
OCH673D
Содержание CITY MULTI
Страница 35: ...35 OCH673D PUMY P112YKME4 BS R2 PUMY P125YKME4 BS R2 PUMY P140YKME4 BS R2 ...
Страница 159: ...159 OCH673D ...