2 SPECIFICATIONS
2.2 Performance Specifications
19
2
2.2
Performance Specifications
The following table lists the performance specifications.
Classification
Item
Specifications
CC-Link side
Station type
Remote device station
CC-Link version
Ver.1.10
Ver.2.00
Extended cyclic setting
2 times setting
Communication speed
10M/5M/2.5M/625K/156Kbps (automatic setting)
Number of occupied
stations
Remote device stations 1 to 4 are occupied
according to the setting of the specification
selection switch.
1 station (RX/RY number of occupied points: 32
points) (RWr/RWw 4/4)
2 stations (RX/RY number of occupied points: 64
points) (RWr/RWw 8/8)
3 stations (RX/RY number of occupied points: 96
points) (RWr/RWw 12/12)
4 stations (RX/RY number of occupied points: 128
points) (RWr/RWw 16/16)
4 stations occupied (RX/RY number of occupied
points: 224 points) (RWr/RWw 32/32)
Number of connectable
modules
64 max.
16 max.
Connection cable
CC-Link dedicated cable (Ver.1.00-compatible)/High-performance CC-Link dedicated cable (Ver.1.00-
compatible)/Ver.1.10-compatible CC-Link dedicated cable
Built-in terminating resistor
Provided (110
)
AnyWireASLINK side
Transmission clock
27.0kHz
Maximum transmission
distance (total length)
200m
Transmission system
DC power supply transmission total frame cyclic system
Connection type
Bus topology (multidrop system, T-branch system, tree branch system)
Transmission protocol
Dedicated protocol (AnyWireASLINK)
Error control
Checksum, double-check system
Number of connected I/O
points
512 points max. (input: 256 points, output: 256 points)
Number of connectable
slave modules
128 max. (varies depending on the current consumption of each slave module)
RAS function
Disconnected transmission cable location detection function, transmission cable short detection
function, transmission cable voltage drop detection function
Transmission cable (DP,
DN)
• UL-listed general-purpose 2-wire cable (VCTF, VCT 1.25mm
2
, 0.75mm
2
, temperature rating: 70
or
higher)
• UL-listed general-purpose wire (1.25mm
2
, 0.75mm
2
, temperature rating: 70
or higher)
• Dedicated flat cable (1.25mm
2
, 0.75mm
2
, temperature rating: 90
)
Power cable (24V, 0V)
• UL-listed general-purpose 2-wire cable (VCTF, VCT 0.75mm
2
to 2.0mm
2
, temperature rating: 70
or
higher)
• UL-listed general-purpose wire (0.75mm
2
to 2.0mm
2
, temperature rating: 70
or higher)
• Dedicated flat cable (1.25mm
2
, 0.75mm
2
, temperature rating: 90
)
Transmission cable supply
current
When using a 1.25mm
2
cable: 2A max.
When using a 0.75mm
2
cable: 1A max.
Maximum number of writes
to EEPROM
100000 times max.
Common
Power supply
Voltage: 21.6 to 27.6VDC (24VDC -10 to +15%), ripple 0.5Vp-p or lower
Recommended voltage: 26.4VDC (24VDC +10%)
Module current consumption: 0.2A
External dimensions
102mm(H)
43mm(W)
96mm(D)
Weight
0.2kg