22
2 SPECIFICATIONS
2.4 Part Names
2.4
Part Names
No.
Name
Description
1)
LED indicator
(CC-Link side)
The status of the bridge module is indicated by the LEDs.
LED name
Description
L RUN LED
(green)
Indicates the CC-Link communication status.
On: Operating normally
Off: Disconnecting (timeout error)
L ERR. LED
(red)
Indicates the CC-Link error status.
On: When station number setting is out of the range
Flashing regularly (0.4-second-intervals): When the station number setting was changed from power-
on.
Flashing irregularly: When the bridge module or CC-Link dedicated cable has been affected by noise.
When on/off of the operation mode setting switch (SW4) and the combinations of mounting
terminating resistor are incorrect.
Off: Operating normally
SD LED
(green)
Indicates the sending status of CC-Link data.
On: Sending data
Flashing: Terminating resistor is not connected in the master module and final station module.
Off: Disconnection or incorrect wiring of CC-Link dedicated cable
RD LED
(green)
Indicates the CC-Link data receiving status.
On: Receiving data
Flashing: Terminating resistor is not connected in the master module and final station module.
Off: Disconnection or incorrect wiring of CC-Link dedicated cable
LED indicator
(AnyWireASLINK side)
LINK LED
(green)
Indicates the link status of the bridge module.
On: During initializing the module or occurring a hardware error. Communication is impossible.
Off: 24VDC power supply is disconnected. Communication is impossible.
Flashing: Operating normally. Communication is possible.
SET LED
(green)
Indicates the address detection status of the bridge module.
On: Automatic address detection in progress
Flashing: Address write in progress
Off: Before or after automatic address detection
ALM LED
(red)
Indicates the error status of the bridge module.
On: DP/DN disconnection, no response from the slave module
Slow flashing (one-second intervals): DP/DN short-circuit
Fast flashing (0.2-second intervals): 24VDC is not being supplied or the voltage is low.
Off: Operating normally
2)
SET switch
Switch for automatic detection of the slave module ID (address) connected AnyWireASLINK.
(
Page 54 Performing the automatic address detection)
3)
CC-Link station number
setting switch
Set the head station number of the bridge module. (
Page 38 Station number setting switch)
4)
Operation mode setting switch
Set the operation mode of the bridge module. (
Page 38 Operation mode setting switch)
5)
Number of transmission points
setting switch
Set the number of transmission points of the AnyWireASLINK. (
6)
CC-Link side terminal block
A terminal block of the CC-Link dedicated cable (
Page 26 CC-Link Side Terminal Block)
1)
2)
5)
7)
3)
4)
6)