38
5 SWITCH SETTING
5.1 CC-Link Side
5
SWITCH SETTING
5.1
CC-Link Side
Station number setting switch
■
Setting method
Set the station number of CC-Link using the rotary switch in the front of the bridge module. Set the station number with power-
off because setting value becomes effective when powered on.
• Set the tens place of the station number to "
10".
• Set the ones place of the station number to "
1".
The number of occupied stations is set by using the number of transmission points setting switch. (
■
Setting range
All switch positions are set to zero (0) when the product is shipped.
Set the station number from 1 to 64. The L ERR. LED turns on when the switch is set to other than 1 to 64.
The station number cannot be set when it is duplicated.
Operation mode setting switch
SW3 is used to set the CC-Link operation mode of the bridge module.
SW4 is used to set the enable/disable status of the built-in CC-Link terminating resistor of the bridge module. (
CC-Link terminating resistor)
All switch positions are set to off when the product is shipped.
Power off and on the bridge module and reset the CC-Link side system after changing the setting value.
Station number
Station number setting switch
10
1
1
0
1
2
0
2
3
0
3
61 (The largest station number when 4 stations are occupied.)
6
1
62 (The largest station number when 3 stations are occupied.)
6
2
63 (The largest station number when 2 stations are occupied.)
6
3
64 (The largest station number when 1 station is occupied.)
6
4
Switch No.
Description
On
Off
SW3
CC-Link operation mode
Ver.2.00
Ver.1.10
SW4
CC-Link terminating resistor
Effective
Not effective