7 SETTINGS BEFORE OPERATION
7.2 Automatic Address Detection
57
7
Automatic address detection execution timing
*1 When turning on Automatic address detection command (RYn1), Automatic address detection command (RYn1) must be turned off after
checking that Automatic address detection flag (RX(n+1)4) turns on and the SET LED is on.
*2 The automatic address detection function is executed for approximately 0.5 seconds after the SET LED turns off.
Slave module alarm signal (RX(n+1)0) and Parameter access error (RX(n+1)2) are maintained until Error
reset request flag (RY(n+1)A, RY(n+3)A, RY(n+5)A, RY(n+7)A, RY(n+D)A) is turned on. Errors are stored in
the appropriate memory areas.
No ID setting or ID in use detected
Parameter access completion flag
(RX(n+1)1)
Slave module alarm signal
(RX(n+1)0)
Parameter access error
(RX(n+1)2)
ON
Batch read executed
Image of
execution
*2
OFF
OFF
ON
ON
OFF
Automatic
Automatic
Automatic
A parameter access
error has occurred.
Turning on Automatic address
detection command (RYn1)
*1
or
long press of the SET switch
Automatic address detection flag
(RX(n+1)4)
SET LED
ON
OFF
ON
Automatic address detection
being executed
The address
being recorded
The LED
on
The LED
flashing
OFF
OFF
Automatic