4 CONNECTIONS
4.7 Terminating Unit
37
4
4.7
Terminating Unit
To ensure more stable transmission quality, connect a terminating unit to the end of a transmission cable (DP, DN).
A
B
Terminating unit
Terminating unit
Terminating unit
Bridge module
Bridge module
Important
Important
Basic
Basic
Connect at least one terminating unit for one AnyWireASLINK line.
Connect it at the farthest end from the bridge module.
Connect one terminating unit at the end of a branch line that exceeds 40m.
[Example]
AnyWire
at the end
Branch line: 40m or longer
The total length of the transmission distance for the AnyWireASLINK system can be calculated from A + B.
Note that the total length should not exceed the maximum transmission distance set for the system to branch lines.
Main line
Main line
The end of a line
The end
of a line
Terminating unit connection
Branch of transmission cables (DP, DN)
Total length