2 SPECIFICATIONS
2.2 Performance Specifications
*1 When the CC-Link operation mode is set to Ver.1.10 by the operation mode setting switch, the number of occupied stations is changed
by the number of transmission points setting switch.
*2 Ver.1.10-compatible CC-Link dedicated cable, CC-Link dedicated cable (Ver.1.00-compatible), and CC-Link dedicated high-
performance cable (Ver.1.00-compatible) cannot be used at the same time. If those cables are used at the same time, normal
transmission is not guaranteed.
In addition, use the terminating resistor according to the type of cable used.
*3 For wiring of 50m or more with 4 wires (DP, DN, 24V, 0V), insert the noise filter for power supply cables between the power supply and
cables. For details, refer to the manual for the AnyWireFILTER (ANF-01) manufactured by Anywire Corporation.
*4 For the relationship between the total length, the wire diameter of transmission cables (DP, DN), and the transmission cable supply
current, refer to the following. On some slave modules with cables, the wire diameter of module-integrated transmission cables (DP, DN)
may be 0.75
or less. However, they can be used without any problem, provided that the diameter of the transmission cables (DP,
DN) meets the requirement below.
Wire diameter of transmission
cables (DP, DN)
Transmission cable supply current
Total length of 50m or less
Total length of 50m to 100m
Total length of 100m to 200m
1.25mm
2
2A max.
1A max.
0.5A max.
0.75mm
2
1.2A max.
0.6A max.
0.3A max.