5 INSTALLATION AND WIRING
5.5 Wiring to a Transmission Cable Terminal Block of the AnyWireASLINK
Wiring product
Applicable wires and cables
Use the following wires or cables connected to the transmission cable terminal block.
Solderless terminal
Bare cables can be connected to the transmission cable terminal block; however, for safety reasons, it is recommended to
connect bar solderless terminals.
Use UL-listed solderless terminals and, for processing, use a crimping tool recommended by their manufacturer.
Classification
Name
Wire
diameter
Type
Material
Temperature
rating
Transmission cable (DP,
DN)
Power cable (24V, 0V)
UL-listed general-purpose 2-wire cable (VCTF,
VCT)
1.25
Stranded wire
Copper wire
70
or higher
0.75
UL-listed general-purpose wire
1.25
0.75
Dedicated flat cable
1.25
90
0.75
Type
Model
Application
Contact
Bar solderless terminal
AI 0,75-8 GY
Processing of a 0.75
wire
PHOENIX CONTACT GmbH & Co. KG
AI 1,5-8 BK
Processing of a 1.25
wire