162
APPX
Appendix 3 Remote Buffer Memory
Parameter area initialization command
■
Address
■
Description
This area is used for clearing the parameter information stored in the non-volatile memory, such as when Non-volatile memory
data error (parameter) (error code: 2010H) occurs.
Setting a fixed bit other than 0 does not cause an error.
(1) 0: No command, 1: With command
If 1: With command is selected for b0, the parameter information of the non-volatile memory is initialized and the initial value
is stored in the non-volatile memory. (The initial value is set to 0: No command.)
The initial values are stored in the monitor area and parameter area after the module is powered on and off.
Name
Address
Parameter area initialization command
0402H
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
(1)
ON
ON
ON
OFF
ON
OFF
OFF
ON
Module power supply remote reset
Address: 0402H bit 0
Parameter area initialization command
Monitor area
Parameter area
Non-volatile memory
Error status flag (RX5)
Initial value
Address: 0403H bit 0
Parameter area initialization completion
SLMPSND instruction
Executed by the NZ2AW1GNAL
Executed by the program
Periodically read and check with the SLMPSD instruction.
Periodically read and check with the SLMPSD instruction.
Setting value A
Initial value
Initial value
During parameter error
Initial value
Setting
value A
Setting
value A
Содержание AnyWire ASLINK
Страница 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Страница 2: ......
Страница 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Страница 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Страница 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Страница 193: ...APPX Appendix 8 External Dimensions 191 A Appendix 8 External Dimensions 43 86 16 8 102 3 6 3 4 0 2 Unit mm ...
Страница 199: ......