152
APPX
Appendix 3 Remote Buffer Memory
Word data points setting
■
Address
■
Description
Set the total number of word data input/output points to be used.
The word data use setting and the relationship between setting and setting value are as follows.
If Word data use setting (address: 0101H) is 0000H (Not use), set this setting to 0000H (Not use) also.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Word data points
setting range error (error code: 1803H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
If Module parameter reflection request flag (RYC) is turned on after writing a combination other than the one that can be set,
Word data setting combination error (error code: 180DH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
The combinations that can be set are the same as those for the word data use setting.
Page 151 Word data use setting
Word data start address setting
■
Address
■
Description
The set value becomes the word data start address.
The settable range is 0 to 511. (Initial value: 0000H)
If word data is not to be used, set the word address to 0.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Word data start
address setting range error (error code: 1804H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
If Module parameter reflection request flag (RYC) is turned on after writing a combination other than the one that can be set,
Word data setting combination error (error code: 180DH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
The combinations that can be set are the same as those for the word data use setting.
Page 151 Word data use setting
Name
Address
Word data points setting
0102H
Setting
Setting value
Not use
0000H (initial value)
2 words (input 1 word, output 1 word)
0001H
4 words (input 2 words, output 2 words)
0002H
8 words (input 4 words, output 4 words)
0003H
16 words (input 8 words, output 8 words)
0004H
32 words (input 16 words, output 16 words)
0005H
64 words (input 32 words, output 32 words)
0006H
128 words (input 64 words, output 64 words)
0007H
256 words (input 128 words, output 128 words)
0008H
512 words (input 256 words, output 256 words)
0009H
1024 words (input 512 words, output 512 words)
000AH
Name
Address
Word data start address setting
0103H
Содержание AnyWire ASLINK
Страница 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Страница 2: ......
Страница 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Страница 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Страница 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Страница 193: ...APPX Appendix 8 External Dimensions 191 A Appendix 8 External Dimensions 43 86 16 8 102 3 6 3 4 0 2 Unit mm ...
Страница 199: ......