APPX
Appendix 2 Remote Register
143
A
Latest alarm ID storage area
■
Device No.
■
Description
This area stores the ID of the slave module that was the target of the latest alarm code when an alarm occurs.
However, 0FFFH is stored when the following alarm occurs.
• DP/DN short error (alarm code: 0CC9H)
• 24V/DP short error (alarm code: 0CCBH)
• Parameter access target module ID error (alarm code: 0D2EH)
• AnyWireASLINK transmission function execution error (alarm code: 0D40H)
• Easy replacement error for one slave module (Parameter access error) (alarm code: 0D82H)
• Non-compatible slave module connection error (alarm code: 0D83H)
• Compatibility inspection error (Excess number of connected slave modules error) (Alarm code: 0D85H)
• Compatibility inspection error (Word data usage setting) (alarm code: 0D86H)
• New ID error (alarm code: 0D92H)
• Excess number of connected slave modules error (alarm code: 0D93H)
The IDs relevant to alarm occurrence are stored in the alarm ID information storage area below.
Page 166 Alarm ID information storage area
After eliminating the cause of the alarm that occurred, turn on Error reset request flag (RY0) to clear the alarm ID.
Number of the IDs of the disconnected modules
■
Device No.
■
Description
This area stores the number of slave module IDs that send no response due to disconnection of the transmission cable (DP,
DN) or a failure in the slave module alone among the IDs of the connected modules. (Up to 256)
If the disconnection error automatic recovery function is enabled, the number of slave modules (number of disconnected
module IDs) from which errors are cleared automatically decreases.
After automatic address detection, the data are updated as soon as a response error is detected.
For details on the disconnected module IDs, refer to the disconnected module ID information storage area below.
Page 165 Disconnected module ID information storage area
Name
Device No.
Latest alarm ID storage area
RWr3
Name
Device No.
Number of the IDs of the disconnected modules
RWr6
Содержание AnyWire ASLINK
Страница 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Страница 2: ......
Страница 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Страница 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Страница 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Страница 193: ...APPX Appendix 8 External Dimensions 191 A Appendix 8 External Dimensions 43 86 16 8 102 3 6 3 4 0 2 Unit mm ...
Страница 199: ......