7 FUNCTIONS
7.13 AnyWireASLINK Version Compatibility Inspection Function
79
7
How to check the error status
If an AnyWireASLINK version compatibility inspection error exists after the inspection, the status will be as follows.
The following are the probable causes of the AnyWireASLINK version compatibility inspection error. Identify the error cause
and take appropriate actions.
• A slave module not supporting word data is connected to the NZ2AW1GNAL.
• The number of connected slave modules exceeds the maximum number of connectable modules.
• Parameter access failed on one or more slave modules.
Clear the AnyWireASLINK version compatibility inspection error, and start the inspection again.
Precautions
• Even when the AnyWireASLINK version compatibility inspection is executed, the configuration information of the slave
modules that is saved in the NZ2AW1GNAL is not updated.
• When an ASLINK version compatibility check is executed, the error information and alarm information are cleared. The
signal to be cleared is the same as below.
Page 137 Error reset request flag
Item
Description
AnyWireASLINK version compatibility inspection error flag
(RX8)
Turns on.
Latest alarm code storage area (RWr2)
The relevant alarm code is stored.
The alarm codes that may occur are listed below.
• Non-compatible slave module connection error (alarm code: 0D83H)
• Compatibility inspection error (Parameter access error) (alarm code: 0D84H)
• Compatibility inspection error (Excess number of connected slave modules error) (Alarm code:
0D85H)
• Compatibility inspection error (Word data usage setting) (alarm code: 0D86H)
Latest alarm ID storage area (RWr3)
The ID of the slave module where the following alarm has occurred is stored.
• Compatibility inspection error (Parameter access error) (alarm code: 0D84H)
For the following alarms 0FFFH is stored.
• Non-compatible slave module connection error (alarm code: 0D83H)
• Compatibility inspection error (Excess number of connected slave modules error) (Alarm code:
0D85H)
• Compatibility inspection error (Word data usage setting) (alarm code: 0D86H)
Version compatibility inspection error ID area (5700H to
577FH)
ID information is registered.
ALM LED
Turns on.
Содержание AnyWire ASLINK
Страница 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Страница 2: ......
Страница 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Страница 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Страница 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Страница 193: ...APPX Appendix 8 External Dimensions 191 A Appendix 8 External Dimensions 43 86 16 8 102 3 6 3 4 0 2 Unit mm ...
Страница 199: ......