CAT 3 Wiring
299
SUMMARY OF CAT 3-SPECIFIC NETWORK CONFIGURATIONS
There are a number of different installation combinations and devices that can run with CAT 3
cables. There are also many exceptions and variations that prevent this from working. The
underlying principles in making the installation work are:
•
The devices connected via CAT 3 must be restricted to 10BaseT operation only.
•
Standard 10/100/1000 auto-negotiation will not guarantee to restrict to 10BaseT with CAT 3
cable and should be avoided. Use manual programming at either, or both, ends of the link.
•
Power over Ethernet may not be guaranteed. Phantom power feed will allow the CAT 3
data pairs to be used.
•
If auto-negotiate fails because one end device is programmed manually, the default is to
used 10BaseT half duplex. Manually setting ports to 10BaseT half duplex will result in a
correctly configured connection.
•
Where multiple devices are connected to a common network port, use of CAT 5 is recom-
mended, with the higher available speeds.
•
The following devices should only be installed with CAT-5E cabling: UC360, 5320e, 5330e
and the 5340e.
To simplify installation, the following installation rules can be applied:
•
Where CAT 3 wiring is used, the network device ports should be manually configured for
10BaseT half duplex. This will allow devices to be moved and maintain their settings as
well as fixing the speed based on the cable run.
•
Phones with a single connection can use CAT 3. Exceptions are the TKB5550 and MiCollab
Client Softphone.
•
The 5550 IP Console should be connected to the network with CAT 5 only.
•
The MiCollab Client Softphone should be connected to the network with CAT 5 only.
•
MiCollab Client is essentially a PC.
•
Phones that connect to the network with an attached PC should use CAT 5, as should the
connection to the PC.
•
Individual PCs can use CAT 3.
•
Servers generally require high-speed connections and should use CAT 5 only.
•
Connections from the ICP WAN port should be via CAT 5 cable.
•
All other connections between the ICP controller to ASU units, to NSU units (SX-200 ICP
only), between NSU (3300 ICP only) should use CAT 5. Note that there is a distance limit
of 30 m on these connections.
•
Connections from T1/E1 (PRI) or BRI circuits can use CAT 5 cable (and RJ45 connector),
but these are considered as telecom connections, so different cable pairs may be used.
•
Connections between network switches and infrastructure should use CAT 5.
Содержание MiVOICE BUSINESS
Страница 1: ...Mitel MiVoice Business RELEASE 7 2 ENGINEERING GUIDELINES ...
Страница 15: ...Chapter 1 ABOUT THIS DOCUMENT ...
Страница 16: ......
Страница 22: ...Engineering Guidelines 8 ...
Страница 23: ...Chapter 2 SYSTEM OVERVIEW ...
Страница 24: ......
Страница 28: ...Engineering Guidelines 14 ...
Страница 29: ...Chapter 3 TYPICAL CONFIGURATIONS ...
Страница 30: ......
Страница 73: ...Chapter 4 PHONES AND VOICE APPLICATIONS ...
Страница 74: ......
Страница 95: ...Phones and Voice Applications 81 Figure 9 ICP Connection Paths and Limitations ...
Страница 100: ...Engineering Guidelines 86 ...
Страница 101: ...Chapter 5 POWER ...
Страница 102: ......
Страница 128: ...Engineering Guidelines 114 ...
Страница 129: ...Chapter 6 PERFORMANCE ...
Страница 130: ......
Страница 135: ...Chapter 7 APPLICATIONS ...
Страница 136: ......
Страница 142: ...Engineering Guidelines 128 ...
Страница 143: ...Chapter 8 EMERGENCY SERVICES ...
Страница 144: ......
Страница 151: ...Chapter 9 IP NETWORKING ...
Страница 152: ......
Страница 167: ...Chapter 10 LICENSING ...
Страница 168: ......
Страница 183: ...Chapter 11 BANDWIDTH CODECS AND COMPRESSION ...
Страница 184: ......
Страница 209: ...Chapter 12 NETWORK CONFIGURATION CONCEPTS ...
Страница 210: ......
Страница 244: ...Engineering Guidelines 230 ...
Страница 245: ...Chapter 13 NETWORK CONFIGURATION SPECIFICS ...
Страница 246: ......
Страница 309: ...Appendix A CAT 3 WIRING ...
Страница 310: ......
Страница 315: ...CAT 3 Wiring 301 Figure 55 CX MX MXe AX and LX Minimum Cable Standard ...
Страница 316: ...Engineering Guidelines 302 ...
Страница 317: ...Appendix B INSTALLATION EXAMPLES ...
Страница 318: ......
Страница 335: ...Appendix C LLDP AND LLDP MED CONFIGURATION EXAMPLES ...
Страница 336: ......
Страница 347: ...Appendix D VOIP AND VLANS ...
Страница 348: ......
Страница 353: ...Appendix E VOIP SECURITY ...
Страница 354: ......
Страница 381: ... ...