Installation and Programming Manual
Mircom Technologies Inc
All Rights Reserved
LT-1034 Rev.1
Page 6 of 54
NOTE : In either Master Mode or Slave Mode, NO detection devices can be installed to the NMC alarm
zone inputs.
Each ISD unit has a unique factory ID called the
‘VID’
number. This
VID
number must be entered into the NMC
Job database and correlated to an
ADDRESS
number which is usually represented by a Suite Number. There are
a couple of methods for entering the
VID
number and these will be discussed in
Section 4.0.
To save time, it is strongly recommended that all ISD information be loaded into the NMC Database
prior to site
installation
via the FIRE-LINKLOAD Windows
®
based download program using the Dealer supplied Barcode
Scanner for the
VID
number entry.
1.3 General Features NMC-100
o
Two initiating device circuits, class B/style B.
o
Power line notification using system compatible ISD-1000 signaling units.
o
One Bell Output Relay for alarm triggering through FACP signal circuit polarity reversal (Slave).
o
One common alarm-actuated relay, form ‘C’.
o
One common trouble-actuated relay, form ‘C’.
o
12V power able to be reset for 4 wire smoke detectors.
o
Keypad entry and control.
o
4-Line LCD Screen for Status/Information Update.
o
Integral battery charger.
o
Battery
Backup.
o
Transformer mounted in cabinet.
o
Cabinet with dead-front construction and lock.
o
Extensive Transient Protection.
1.4 General Features ISD-1000
o
Addressable
Multi-Device
Networking.
o
Plugs into any standard 120V AC outlet.
o
24 Hour supervised rechargeable battery standby power.
o
Silence able Piezo (10 Minute Timer – Canadian Version only).
o
Becomes a ‘BEACON’ when it is unplugged in the alarm state.
o
Is mobile during a fire so that Firemen can locate it.
1.5 Application
ULC 527 - Accessory to an existing fire alarm control panel for supplemental fire signaling in residential sleeping
areas
ULC S545 – Residential Fire Warning System
UL985 – Household Fire Warning System with UL464 fire signaling
1.6 Specifications
This document applies to the following products and product revisions:
•
NMC-100 Rev 1.2A.
•
ISD-1000 Rev 2.0A.
•
PPC-600 Rev 1.0A.
ISD-1000 information:
Listed to UL 985: ISD-1000-MW, ISD-1000-MR