Installation and Programming Manual  

  

 

 

Mircom Technologies Inc           

 All Rights Reserved  

     LT-1034 Rev.1 

 

Page 34 of 54 

Enter the 8 character 

VID

 number found on the back of the ISD unit, on the Barcode Label, followed by 

ENT.

 

 
Follow the procedure outlined in 

Section 5.13 

for 

Enrolling

 an 

ISD or see procedure below

.

 

 
 
 

NOTICE: FOR ENROLLING SINGLE ISDs, FOLLOW THESE STEPS: 

 

1.  Go to ‘EDIT ADDR’ menu (see Section 5.12) 
2.  Press ‘8’ and ‘9’ simultaneously 
3.  Go to the ‘VIEW MISSING’ menu and press ENT 
4.  Choose the unenrolled ISD you want to enroll onto the network and press ‘3’  (‘3’ = E for ENROLL) 
5.  The NMC will attempt to enroll this device.  

If it is successful, a message will appear ‘ENROLL SUCCESSFUL!!’ and the ISD will be moved to 
the enrolled ISDs category. If the enrollment is not successful ‘ENROLL FAILED!’ will appear on 
the display. You should then verify this units VID number. If it is correct, then verify why the NMC 
cannot see it on the network. (Location-unplugged? 12V Halogen present? faulty ISD? etc.). 
 
 

 

5.16 Setting the System Parameters 

 
The NMC has several system parameters that may be adjusted 

globally

 to suit specific needs or applications. 

 

Please note however that adjusting these parameters may violate ULC, UL, NFPA and/or local 

jurisdictional (AHJ) fire alarm codes and standards. 

The global programmable parameters are:

 

 

ISD Signal Rate 

 

Signal Silence Inhibit 

 Trouble 

Notification 

 

Auto Alarm Silence 

 

Clear Trouble and Alarm Logs 

 

ISD Signal Rate

 

Changes the ISD audible alarm rate from 

Temporal

 [default] to 

March Time

 or to 

Continuous

. All ISDs will 

alarm at the same chosen signal rate.  
 

Signal Silence Inhibit

 

Changes the Silence Inhibit feature on the NMC from disabled [default] to enable. If left disabled, the ISDs can be 
silenced from the NMC keypad at any time during the alarm condition. If enabled, the ISDs may be silenced by 
pressing the Alarm Silence button on the NMC keypad 

after

 the selected time has elapsed. The selectable times 

are: 1 min. [default], 5, 10 and 20 minutes.   
(In Canada, this will NOT effect the operation of the 10 minute silencing feature on the ISDs). 
 

Trouble Notification

 

Allows for trouble conditions to be reported by the NMC on the following conditions: 

 ISD 

Missing 

 

 

ISD Battery Trouble (Low or Missing) 

 NMC 

Date/Time 

Loss 

 

The above conditions are factory default to put the NMC into trouble mode if any of these conditions are 
present.  

 

Содержание Fire-Link ISD-1000 Series

Страница 1: ...in Canada Subject to change without prior notice U S A 60 Industrial Parkway Cheektowaga New York 14227 Tel 1 888 660 4655 Fax 1 888 660 4113 www mircom com FIRE LINK LT 1034 Rev 1 100207 October 200...

Страница 2: ......

Страница 3: ...iring the PPC 600 Passive Phase Coupler 18 4 0 ISD 1000 INSTALLATION 19 4 1 ISD 1000 Installation 19 4 2 Installation Checklist Quick Start 20 5 0 NMC PROGRAMMING 21 5 1 The Menu Tree 21 5 2 User Pass...

Страница 4: ...8 ISD Sound Tests 41 5 29 Global ISD Piezo Test 41 5 30 Global ISD Drill Test 42 5 31 Single ISD Piezo Test 42 5 32 Single ISD Drill Test Access Level 1 43 5 33 Reset All ISDs Access Level 3 43 5 34 C...

Страница 5: ...ve allowable FCC DOC limits o AC Variable Speed Motors such as elevator motors connected on the residential 220 volt feed and stepped up to 480V or 600V can generate a lot of noise back onto the domes...

Страница 6: ...The NMC is in constant communications with all of the ISD units Under normal conditions the NMC interrogates each ISD for status A trouble condition occurs on the NMC if any ISD is unplugged and loses...

Страница 7: ...uit polarity reversal Slave o One common alarm actuated relay form C o One common trouble actuated relay form C o 12V power able to be reset for 4 wire smoke detectors o Keypad entry and control o 4 L...

Страница 8: ...ing System Units The ISD 1000 In suite Signaling Devices are considered modules of the NMC 100 Control Unit of the Fire Link system The PPC 600 Passive Phase Coupler is designed to meet UL508 and CSA...

Страница 9: ...support with a lead acid rechargeable battery The required battery is a 12V 12AH SLA Battery capable of providing 24 hours of standby power Periodic inspection for damage and the batteries ability to...

Страница 10: ...t in a hazardous location Install the unit near flammable explosive or corrosive chemicals or materials Install the unit where it will be subjected to excessive dust or dirt Install the unit near flam...

Страница 11: ...any knock outs Do not modify the enclosure in any way 4 Attach all conduits to the enclosure 5 Using a maximum of 12AWG stranded wire install the NMC on a separate 120VAC 15 Amp service Separation of...

Страница 12: ...ions When the NMC is triggered for alarm by the FACP either in Master Mode or Slave Mode NO other initiating devices may be wired to the NMC zone inputs 2 2 Master Mode In Master Mode when an alarm oc...

Страница 13: ...normal state causing the NMC to silence the ISDs and return from alarm state to normal state If the FACP re alarms this will cause the NMC to re alarm as well Connect the Signal Circuit wiring of the...

Страница 14: ...mpatible smoke detector Smoke detectors installed in Stand Alone Mode should be tested at least once per year as per manufacturer s specifications Four Wire 12V DC Resettable Smoke Detector Power Term...

Страница 15: ...ate through and make selections in the various menus NOTE While in Programming Mode a trouble condition will occur on the NMC but the local piezo will not sound WARNING THE NMC WILL NOT RESPOND TO ANY...

Страница 16: ...ss the 1 key 3 Press 2 key twice until B appears 4 Press 3 key until E appears and so on When finished press the ENT key to accept Use the above keys in the same manner to enter these special characte...

Страница 17: ...nications medium one that is being constantly changed by the addition or movement of other electrical equipment the NMC communications polling routine will establish new routes if required to maintain...

Страница 18: ...ouble mode Devices Missing Loss of Date Time Input the date and time Input ISD Job File via download program or manually enter ISD info VID and Address In menu enroll Auto Program ISD s Investigate an...

Страница 19: ...The PPC can not couple signals from the load side of one transformer to its line side and then to the load side of another Therefore ONE NMC and ONE PPC are required for EACH power distribution transf...

Страница 20: ...accuracy and then downloaded to the NMC see FIRE LINK Load manual each ISD can now be installed in its pre assigned suite This should be done by a technician from the installing company The procedure...

Страница 21: ...s suite number and check box if a message unit o Scan barcode VID provided on back of ISD unit o Write this suite number in space provided on back housing of ISD unit Use non smearing ink felt pen o R...

Страница 22: ...Installation and Programming Manual Mircom Technologies Inc All Rights Reserved LT 1034 Rev 1 Page 21 of 54 5 0 NMC PROGRAMMING 5 1 The Menu Tree See Figures 8 13 below for the NMC menu tree...

Страница 23: ...Installation and Programming Manual Mircom Technologies Inc All Rights Reserved LT 1034 Rev 1 Page 22 of 54 FIGURE 8 Access Level 1 Menu Tree Sheet 1 FIGURE 9 Access Level 2 Menu Tree Sheet 2...

Страница 24: ...Installation and Programming Manual Mircom Technologies Inc All Rights Reserved LT 1034 Rev 1 Page 23 of 54 FIGURE 10 Access Level 3 Menu Tree Sheet 3...

Страница 25: ...Installation and Programming Manual Mircom Technologies Inc All Rights Reserved LT 1034 Rev 1 Page 24 of 54 FIGURE 11 Access Level 3 Menu Tree Sheet 4...

Страница 26: ...Installation and Programming Manual Mircom Technologies Inc All Rights Reserved LT 1034 Rev 1 Page 25 of 54 FIGURE 12 Access Level 3 Menu Tree Sheet 5...

Страница 27: ...Rights Reserved LT 1034 Rev 1 Page 26 of 54 FIGURE 13 Access Level 3 Menu Tree Sheet 6 Note the pass code access levels for the various menu options The various menu options will not be made available...

Страница 28: ...evels 1 2 and 3 Pass code entry is the first menu option and must be entered before any other menu options can be entered 5 3 Entering Programming Mode To access the menu screens press the key This wi...

Страница 29: ...odel Versions of firmware 1 US UL985 200 sec trouble delay NO 10 min silencing timer 5 min silence inhibit 10 min auto alarm silence timer 2 Canadian ULC527 90 sec trouble delay 3 Demo 15 sec trouble...

Страница 30: ...ired after an NMC firmware update Access Level 3 To reset the Factory Defaults select CONFIGURE CONFIGURE NMC NMC NETWORK FACTORY DEFAULT There will be a 1 second delay between displays of Resetting P...

Страница 31: ...identity of the ISD device This process will retrieve the VID number for ONE UNIT ONLY and ONLY ONE UNIT AT A TIME Unplug the ISD and repeat these steps with all other ISD units NOTE This process wil...

Страница 32: ...uld appear 5 13 Auto Programming Enrolling ISDs onto the Network Access Level 3 After any ISD one or more has been entered into the NMC database either manually or via the FIRE LINK Load program it mu...

Страница 33: ...play the list of ISDs under this category Select an ISD and press ENT to select and then press 3 to enroll The window should display ENROLL SUCCESS This will take you back to the first window to selec...

Страница 34: ...e Use this option to remove an inoperable ISD unit as well before installing a replacement unit Leave or re install the ISD into any AC outlet Select CONFIGURE CONFIGURE ISD REMOVE ISDS Use or to sele...

Страница 35: ...ted globally to suit specific needs or applications Please note however that adjusting these parameters may violate ULC UL NFPA and or local jurisdictional AHJ fire alarm codes and standards The globa...

Страница 36: ...ons to be ignored by the NMC NMC Date Time Loss parameter will cause a trouble condition on the NMC at power up if the Date Time is lost due to a complete NMC power failure Complete NMC power failure...

Страница 37: ...will change whether or not the NMC will keep the ISDs in alarm until a manual action is taken or if the NMC will automatically silence the ISD alarms after 10 minutes The default setting is disabled...

Страница 38: ...rting function will not The Bypass feature is intended as a temporary removal of one ISD or more that require in suite filters installed for 12V Halogen noise WARNING Disabling this feature or increas...

Страница 39: ...invert the ISD Address selection from Enabled to BYPASSED or visa versa Here BYPASSED means that the Missing ISD Trouble notification on the NMC will be disabled for this ISD or multiple ISDs chosen B...

Страница 40: ...otification feature WARNING By disabling this feature the system will not be able to provide notification of a complete system power failure when power is restored All future events will be stamped wi...

Страница 41: ...tat 5 26 Testing the NMC Alarm and Trouble Relays Access Level 2 Use this menu selection to test the NMC Alarm and Trouble Relays ON will energize both relays and OFF will de energize both relays Sele...

Страница 42: ...n alarm mode without the test reporting feature The Drill Test will alarm the ISDs at the alarm sounding rate that they are currently set to default being Temporal Both the PIEZO TEST and DRILL TEST c...

Страница 43: ...selection to test the piezo operation of a single ISD Select TESTS ISD TESTS TEST SINGLE ISD TEST PIEZO PIEZO Use the UP DOWN keys to select the desired unit Press ENT to start test When the test has...

Страница 44: ...al 5 34 CONNECT to NMC From Laptop Access Level 3 This selection is used to connect the NMC to a laptop to download the FIRE LINKload Windows based job file data A DB9 serial port cable is needed to c...

Страница 45: ...top can be used to initiate the transfer of data The NMC will go into trouble mode but the piezo will not sound See FIRE LINKload Help document for further available functions from this linked program...

Страница 46: ...P should have an alarm condition initiated to insure that the NMC is put into alarm condition via the FACP dry alarm contact or through the sounding of the FACP signal circuit NMC Bell Output Relay Th...

Страница 47: ...rand This battery has been properly sized to the current demands of the Rx and Tx functions during 24 standby operations 7 3 ISD Battery Replacement Refer to Section 1 12 for proper battery type and p...

Страница 48: ...once safely outside If there are infants older adultsor family members with mobility limitations make sure that someone is assigned to assist them in the fire drill and in the event of an emergency A...

Страница 49: ...location You don t want to have to search for it during a fire Always choose the escape route that is safest the one with the least amount of smoke and heat but be prepared to escape through toxic sm...

Страница 50: ...of the 12V halogen This will either be at the switch or in the base of the lighting unit Some halogens are plug in units Use the plug in type filter for these Another solution would be to replace the...

Страница 51: ...ssages Sys Error 1 Indicates a problem with the Network Controller on the NMC main board Sys Error 2 Indicates a problem with the system EEPROM on the NMC Main Controller Sys Error 3 Indicates a probl...

Страница 52: ...system operates from standby batteries it is possible for the batteries to fail Even if the batteries have not failed they must be full or close to fully charged In the case of the ISD 1000 rechargeab...

Страница 53: ...ability to respond to the warnings in a timely manner If the system is monitored the response may not occur in time enough to protect the occupants or their belongings Component Failure Although every...

Страница 54: ...the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arising out of any other abuse mishandling or imprope...

Страница 55: ...rrent market price of the replacement product will be charged for each replacement unit WARNING Mircom Technologies Ltd recommends that the entire system be completely tested on a regular basis Howeve...

Страница 56: ...Tel 905 660 4655 Fax 905 660 4113 Mircom 2007 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway PMB 278 Cheektowaga NY...

Отзывы: