Installation and Programming Manual
Mircom Technologies Inc
All Rights Reserved
LT-1034 Rev.1
Page 37 of 54
5.20 Clearing the Alarm and Trouble Logs
Access Level 3
This menu selection will clear the contents of the Trouble and/or Alarm Logs. This process is irreversible in that
once the log is cleared; the previous contents
CANNOT
be recovered.
Select [
CONFIGURE
]
[
CONFIGURE NMC
]
[
SYST PARAMETERS
]
[
CLEAR LOG
]. Press
NXT
to toggle
between TROUBLE or ALARM. Press
ENT
to accept.
5.21 Setting the ISD Missing Trouble Notification
Access Level 3
Use this menu selection to enable or disable the global ISD Missing Trouble Notification feature or to ‘
Bypass’
one or more individual ISDs from the network.
Bypassing
will create a trouble condition on the NMC whereas the
“
Never Reporting
’ function will
not
. The Bypass feature is intended as a temporary removal of one ISD, or more,
that require in-suite filters installed for 12V Halogen noise.
WARNING: Disabling this feature or increasing lapse times could VIOLATE UL/ULC and/or local AHJ
fire codes. If the ISD Missing Trouble Notification is disabled, the system will not be able to determine if
an ISD has been unplugged and/or removed
.
Select [
CONFIGURE
]
[
CONFIGURE NMC
]
[
SYST PARAMETERS
]
[
TROUBLES
]
[
MISSING
DEVICES
].
CLEAR LOGS
>TROUBLES
UP DWN ENT BCK
ISD SIGNL RATE
SIG SIL INHIBIT
AUTO ALRM SIL
UP DWN ENT BCK
NMC NETWORK
>SYST PARAMETERS
CONFIG RELAY
UP DWN ENT BCK
>CONFIGURE NMC
CONFIGURE ISD
UP DWN ENT BCK
ADMINISTRATION
TESTS
>CONFIGURE
UP DWN ENT BCK
>CLEAR TRBL LOG
CLEAR ALRM LOG
NXT ENT BCK
ISD SIGNL RATE
SIG SIL INHIBIT
AUTO ALRM SIL
UP DWN ENT BCK
NMC NETWORK
>SYST PARAMETERS
CONFIG RELAY
UP DWN ENT BCK
>CONFIGURE NMC
CONFIGURE ISD
UP DWN ENT BCK
ADMINISTRATION
TESTS
>CONFIGURE
UP DWN ENT BCK