Installation and Programming Manual
Mircom Technologies Inc
All Rights Reserved
LT-1034 Rev.1
Page 10 of 54
2.1 Installing the NMC-100
This installation should be performed by a qualified Electrician. Observe the General Precautions stated above.
1. Locate the NMC in a suitable location in close proximity to the existing FACP.
2. Remove the front door and dead front panel and mount the NMC to the wall or any flat surface using the
4 mounting holes on the back side of the enclosure.
3. Locate all conduit entries into the NMC prior to removing any knock-outs. Do not modify the enclosure in
any way.
4. Attach all conduits to the enclosure.
5. Using a maximum of 12AWG stranded wire, install the NMC on a separate 120VAC 15 Amp service.
Separation of high voltage and low voltage wiring is required within the NMC enclosure. High voltage and
low voltage wiring must not be placed in the same raceway.
6. In the low voltage wiring zone, the battery leads need to be routed separately from power-limited low
voltage internal connections.
7. Using a maximum of 18AWG and a minimum of 24AWG for all zone, input and output wiring.
A locking device is recommended on this service. If no spare circuit is available, power may be obtained from the
FACP circuit as the NMC is considered an accessory to the FACP.