5.18 Setting the Signal Silence Inhibit
Access Level 3
Use this menu selection to set the global Signal Silence Inhibit feature. If the Signal Silence Inhibit feature is
disabled, the ISDs
can
be silenced at any time from the NMC keypad during the fire alarm condition.
If the NMC is wired to trigger an alarm via the bell output relay, the ‘Signal Silence’ button on the NMC will
NOT function.
Select [
CONFIGURE
]
[
CONFIGURE NMC
]
[
SYST PARAMETERS
]
[
SIG SIL INHIBIT
].
Press
NXT
to toggle between options.
These options are: Disabled (default), if enabled : choose 1 min, 5 min or 10 min. Press
ENT
to accept.
Under UL985, the option should be set for 5 min as default.
5.19 Setting the Auto Alarm Silence Feature
Access Level 3
This menu selection will change whether or not the NMC will keep the ISDs in alarm until a manual action is taken
or if the NMC will automatically silence the ISD alarms after 10 minutes. The default setting is disabled meaning
the NMC will keep the ISDs in alarm until action is taken. When enabled, the 10 minutes becomes the option only.
Under UL985, the option should be set for the 10 min auto alarm silence.
Select [
CONFIGURE
]
[
CONFIGURE NMC
]
[
SYST PARAMETERS
]
[
AUTO ALRM SIL
]. Press
NXT
to
toggle between options. Press
ENT
to accept.
AUTO ALRM SIL
10 MINUTES
ENT BCK
ISD SIGNL RATE
SIG SIL INHIBIT
>AUTO ALRM SIL
UP DWN ENT BCK
NMC NETWORK
>SYST PARAMETERS
CONFIG RELAY
UP DWN ENT BCK
>CONFIGURE NMC
CONFIGURE ISD
UP DWN ENT BCK
ADMINISTRATION
TESTS
>CONFIGURE
UP DWN ENT BCK
INHIBIT TIME
MINUTES: 5
NXT ENT BCK
SIGNAL SILENCE
INHIBIT:
ENABLED
NXT ENT BCK
ISD SIGNL RATE
>SIG SIL INHIBIT
AUTO ALRM SIL
UP DWN ENT BCK
NMC NETWORK
>SYST PARAMETERS
CONFIG RELAY
UP DWN ENT BCK
>CONFIGURE NMC
CONFIGURE ISD
UP DWN ENT BCK
ADMINISTRATION
TESTS
>CONFIGURE
UP DWN ENT BCK