5.28 ISD Sound Tests
Once installed onto the network, the ISDs can be tested either individually or globally. The Piezo Test allows for a
‘Pass/Fail’ report whereas the ‘Drill Test’ does
NOT.
PIEZO TEST
allows for automatic testing of the ISD’s piezo. This test will turn on the ISD’s piezo for a brief
moment and monitor the sound output. This test can be performed without the presence of a technician at the
ISD.
NOTE: This test monitors the sound output from within the ISD. It cannot determine if there is any
obstruction, such as tape, over the ISD grill or around the ISD.
During the test, the piezo will turn on for a
fraction of a second then turn off if the sound level is sufficient. If the sound level is not sufficient, the piezo may
remain on for up to 5 seconds. A report can be obtained from the NMC via the FIRE-LINKLOAD program showing
the results of this test for archival purposes.
DRILL TEST
allows for testing of the ISD in an alarm mode
without the test reporting feature.
The Drill Test will
alarm the ISDs at the alarm sounding rate that they are currently set to (default being Temporal).
Both the
PIEZO TEST and DRILL TEST
can be performed globally or individually by ISD suite number.
5.29 Global ISD Piezo Test
Access Level 1
Use this menu selection to test the piezo operation of all ISDs on the network at once.
Select: [
TESTS
]
[
ISD TESTS
]
[
TEST ALL ISDS
]
[
TEST ALL PIEZOS
].
Press
CONT
to start test.
When the test has concluded, a ‘Passed/Failed’ message will appear. If any ISD’s fail, a list of failed ISD units, by
suite number, will appear. These failed units should be investigated as soon as possible. The test switch should
be pressed to test the piezo sounding. If the unit does not sound, it should be replaced immediately with another
ISD unit after programming and enrolling it. The failed unit will have to be removed from the network as well.
A hard copy report can be generated by the NMC via the FIRELINKLOAD database program for reporting/history
purposes.
TEST SINGLE ISD
>TEST ALL ISDS
RESET ALL ISDS
UP DWN ENT BCK
NMC TESTS
>ISD TESTS
UP DWN ENT BCK
DISPLAY VERSION
ADMINISTRATION
>TESTS
UP DWN ENT BCK
PIEZO TEST
CONT BCK
>TEST ALL PIEZOS
DRILL TEST
UP DWN ENT BCK