9.3 Drive Control Unit
ATECH / ZAPI
•7) VMN LOW
7) VMN LOW
•Test in rest state and during ride until VMN is pulsed out to up to 80%;
•If contactors are open, voltage at VMN connection normally amounts to 50% VBatt. If
this voltage value is insufficient (< 30% VBatt) an alarm is output. Possible causes:
•
a) Master contactor (if fitted) does not close or is not connected at all
•
b) Short-circuit between connection VMN and -Batt (metal particles or
•
other.) (disconnect cable at connection VMN, switch on, error disappears)
•
c) Power MOSFET short circuited or permanently triggered by logic;
•
c) Power MOSFET short-circuited or permanently triggered by logic;
•
(disconnect cable at connection VMN, switch on, error persists, replace
•
controller)
•
d) Bypass contactor (if fitted) stuck or opens too slowly
)
yp
(
)