Page 64
MiniRanger Plus – INSTRUCTION MANUAL
7ML19981CJ02
*refer to associated transducer manual.
Symptom
Cause
Action
Readings erratic
Echo conficence weak
Liquid surface agitated
Material fiiling
Electircal noise
Aigtator blades
Refer to P805, P807
Decrease measurement
response P003
Enable filter, echo verification
Relocate transducer*
Check P807 under quiescent
conditions, noise should be 15
dB
Transducer cable must be in
grounded metal conduit and
cable grounded only at TB-1*
Enable echo verification, P003
Reading "EEEE"
Reading too large
Re-calibrate
Reading response slow
P003 setting
Increase response if possible
Reads correctly, but occa-
sionally reads high when ves-
sel is not full
Detecting close range echo or
ringdown
Increase blanking
Incraese shot measurement
threshold, P804
Transducer mounting*
High level reading lower than
material level
Material is within near blanking
zone
Echo multiple being processed
Decrease blaking P900 (limit to
transducer minimum range*)
or raise transducer.