![Milltronics miniranger plus Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/milltronics/miniranger-plus/miniranger-plus_instruction-manual_1796962045.webp)
7ML19981CJ02
MiniRanger Plus – INSTRUCTION MANUAL
Page 41
Parameter
Directions
Description
Reset
P999
master reset
P
rogr
am
P001
enter ’4’
mode of measurement = high level
switch
P002
enter ’2’
materal = solids
P003
enter ’2’
measurement response = 1 m/min.
Note: this is the next fastest response
rate that would satisfy the given maxi-
mum filling rate
P004
enter ’104’
the transducer model purchased with
this system is an XPS-15
P005
enter ’1’
unit = meters
P006
enter ’4’
empty distance = 4 m (nominal value)
P007
enter ’4’
span = 4 m (nominal value)
P111-1
enter ’1’
level alarm, relay 1
P112-1
enter ’1’
relay 1, on setpont = 1 m
P113-1
enter ’2’
relay 1, off setpoint = 2 m (nominal
value, 1 m deadband)
Run
press run to start normal operation