Page 58
MiniRanger Plus – INSTRUCTION MANUAL
7ML19981CJ02
MT-01
Hold Message
P800 Near Blanking
Sets the amount of blanking as measured from the transducer face and extending into
the measurement range. Refer to Blanking on page 34.
Enter value referenced from the face of the transducer in units of P005.
P801 Range Extension
Sets the amount of range extension as measured from the empty distance (P006) and
extending into the far end blanking. Refer to Blanking on page 34.
Enter as a % of P006, the distance below empty not blanked.
P802 Submergence Transducer
When using a transducer with a submergence shield, set entry to `1' to enable
submergence feature. Refer to Pump Control Application on page 46.
P804 Confidence Threshold
The minimum echo confidence in dB that either the short or long echo must meet in order
to prevent a loss of echo condition and the expiration of the fail-safe timer (P070).
short
minimum echo confidence for short pulse echoes; those within the short
pulse echo range.
long
minimum echo confidence for long pulse echoes.
entry:
## : ## (short : long)