7ML19981CJ02
MiniRanger Plus – INSTRUCTION MANUAL
Page 63
*refer to associated transducer manual.
Symptom
Cause
Action
...continued
Transducer location for aiming:
Poor installation
Moved my material or vibration
Flanging not level
Transducer malfunction:
Temperature too high
Physical damage
Excessive foam on liquid face
Relocate or re-aim transducer
for maxium echo confidence,
P805
Check P300, P805, P807
Inspect
Use foam deflector or stilling
well or relocate
Reading does not change, but
the level does
MiniRanger Plus processing
wrong echo:
i.e. vessel wall, sturctural mem-
ber, stationary agitator,
material hang-up, or rathole.
Transducer ringdown, reading
high level
Re-aim transducer*
Check standpipe for internal
burrs or welds
Mounting need only be hand
tight*
Increase blaking, P800
Raise short measurement con-
fidence threshold, P804
Measurement is consistently
off by a constant amount
Measurement offset
Refer to P650
Reading error progressively
worsens with distance
Atmosphere other than air or
stratified
Refer to P651
Screen Blank
Loss of Power
Check power wiring