Page 54
MiniRanger Plus – INSTRUCTION MANUAL
7ML19981CJ02
P606 Time Units
Defines the time element of the flow units.
e.g. If flowrate is displayed in millions of gallons / day, and the maximum flowrate is
376,500,000 gallons / day, enter "376.5" for Maximum Flow (P604) and "4" for Time Units
(P606).
P610 Head Breakpoints
The head breakpoints for which flowrate is known.
These are the values in the Span for which flowrates are known. See Open Channel
Monitoring (OCM) on page 53 for a description of how to specify breakpoints.
P611 Breakpoint Flowrates
The flowrate corresponding to each Head Breakpoint entered.
These are the flowrates for the related breakpoints. . See Open Channel Monitoring
(OCM) on page 53 for a description of how to specify breakpoints.
P640 Remote Totalizer Multiplier
Multiplies the number of OCM units needed per relay "click."
Enter the factor (powers of 10 only) by which actual volume is divided, prior to Remote
Totalizer count increment.
e.g. for a Remote Totalizer update by 1000's of volume units, enter 3.
Values
1
seconds
2
minutes
3
hours
4
days (default)
Values
Range: 0.0 to 15.0 meters (or equivalent units as defined by P005)
Values
Range: 0.000 to 30,000
Note:
When the MiniRanger is put into program mode the cumulative total used
to trigger the next totalizer relay "click" is reset to 0. This disruption will cause the
external totalizer to read lower than the actual OCM total, depending on the
number of times programming mode is used and the amount of time spent there.