Page 44
MiniRanger Plus – INSTRUCTION MANUAL
7ML19981CJ02
Parameter Settings
Now in the RUN mode, the reading value and mA output will represent volume in cubic
feet.
Parameter
Description
Instructions
P001
Operation
Enter "1" for level.
P002
Material
No entry required (preset for liquid)
P003
Measurement
Response
Enter "4" for 100 m/min. (Failsafe Timer = 0.1 minutes)
P004
Transducer
Enter "101" for XCT-8
P005
Units
Enter "4" for feet.
P006
Empty
Enter "4.5" for 4.50 ft (3 ft diameter plus 1.5 ft in stand-
pipe)
P007
Span
Enter "3" for 3 ft (vessel diameter).
P070
Failsafe Timer
No entry required (preset by P003).
P050
Tank Shape
Enter "7" for horizontal cylinder with parabolic ends.
P051
Max. Volume
Enter "117" for 117 cubic feet (use vessel fabricators
value).
P052
Tank Dimension A
Enter "1.5" for 1.5 ft (the horizontal length, excluding par-
abolic ends)
P200
mA Range
No entry required. (preset to "2" for 4-20 mA output).