MiniRanger Plus – INSTRUCTION MANUAL
Page 57
Status A
1 character, $0 to $F (convert to binary, e.g. temp, echo, and cable OK, not priority)
MSB
LSB
# # #
#
0 = reserved
1 = loss of echo (f.s. expired)
1 = transducer cable fault
0 = reserved
Status B
1 character, $0 to $F (convert to binary, e.g. scan point is in high alarm)
MSB
LSB
#
#
#
#
1 = low low alarm
1 = low alarm
1 = high alarm
1 = high high alarm
Status C
1 character, $0 to $F (convert to binary, e.g. scan point is not in rate or band alarm)
MSB
LSB
#
#
#
#
0 = reserved
0 = reserved
0 = reserved
0 = reserved
Field Name
Definition
Temp
2 characters, $32 to $FA (convert to decimal and subtract 100, e.g.
temperature = 20°C)
Percent
5 characters, 00.00 to 9999. (e.g. current level = 85.00% of span,
EEEE. = field overflow)
End Of Message
CR ($0D)