Page 38
MiniRanger Plus – INSTRUCTION MANUAL
7ML19981CJ02
Pump Control Application
The basic difference between a simple level application and a pump control application is
that the relays assigned to pump function (P111) are normally de-energized (off) and
energized when required to run the pump. In the program mode, pump relays are held de-
energized.
Pumps can be programmed to work independently or in lead/lag fashion. Refer to 36.
In applications where flooding is possible, a submersible transducer should be used. The
submersible transducer's air cavity insures that a high level reading is maintained rather
than establishing a loss of echo condition, when the liquid level reaches the transducer.
When using a submersible transducer, set P802 = 1.
Example
The application is to control the level in a wet well. It is required that the level be
displayed in centimetres. The transducer is mounted at 3.6 m from the bottom and is
equipped with a submergence coupling as there is possibility of flooding in the well. Two
pumps are to be controlled by the MiniRanger Plus in lead / lag fashion. The first pump to
start at 1 m and the second pump to start at 2 m. Both pumps are to stop at 0.25 m. The
maximum estimated filling rate is 1 m/min. In the event of a loss of echo, a fail-safe low
after 6 sec is required to protect the pumps from running dry.
P006
3.6 m
P007
3.0 m
relay 2, pump on
P112-2
1.0 m
P113-1&2, 0.25 m
relay 1, pump on
P112-1
2 m
relay 1&2,
pumps off