26
If relay function is set to CBFP (Circuit Breaker Failure Protection) the following menu is
displayed:
Set the value for the time delay of CBFP. This output relay is
activated, if after the activation of the trip relay, the fault has not been
cleared for longer than this delay.
Set if Aux 1 or 2 input is included as fault condition. Prolonged
activation or latched Aux input could cause the undesirable activation
of CBFP relay.
Maintenance Mode Menu
Heading of Maintenance Mode menu. Press Enter to enter submenu
content.
Press Enter once, output 1 blinks, press Up/Down to toggle the output
status. Press Enter again to test output 2, and subsequently for output 3
and 4. Press Esc to exit.
COMMUNICATION Menu
Communication setting is applicable to the RS485 port on the rear terminals of the relay (the front
panel RS232 port has fixed communication settings: 38400bps, 1 stop bit, even parity, address 1).
Heading of COMMUNICATION menu. Press Enter to enter submenu
content.
tAux 1(Alarm)?
Yes
Assign Aux 1 input alarm to the output relay.
tAux 2(Alarm)?
Yes
Assign Aux 2 input alarm to the output relay.
TCS(Alarm)?
Yes
Assign TCS alarm to the output relay.
Demand(Alarm)? Yes
Assign Demand alarm to the output relay.
I2>?
Yes
Assign I2> alarm to the output relay.
I2>>?
Yes
Assign I2>> alarm to the output relay.
CB Close?
Yes
Assign CB Close signal to the output relay.
CB Fail?
Yes
Assign CB Fail alarm to the output relay.
Reclsr Run?
Yes
Assign Recloser run alarm to the output relay.
Reclsr Locked?
Yes
Assign Recloser locked alarm to the output relay.
CB Alarm?
Yes
Assign CB Alarm to the output relay.
Delay
200ms
Include Aux?
No
8.
COMMUNICATION
7.5 Maint mode
(Prot disabled)
Output 1 2 3 4
Test 0 0 0 0