24
If Reset is selected, the following menu is displayed:
If Blocking is selected, the following menu is displayed:
Block I>?
Yes
Set to yes to enable blocking of I>
Block I>>?
Yes
Set to yes to enable blocking of I>>
Block I>>>?
Yes
Set to yes to enable blocking of I>>>
Block Io>?
Yes
Set to yes to enable blocking of Io>
Block Io>>?
Yes
Set to yes to enable blocking of Io>>
Block Io>>>?
Yes
Set to yes to enable blocking of Io>>>
Block Thml OL?
Yes
Set to yes to enable blocking of Thermal Overload
Block I2>?
Yes
Set to yes to enable blocking of I2>
Block I2>>?
Yes
Set to yes to enable blocking of I2>>
If TCS (trip circuit supervision) is selected, the following menu is displayed:
Set the value for the time delay of TCS. TCS alarm triggers when
the input is deactivated for longer than the time delay. TCS
function is enabled when the trip output relay R1 is not energized.
Input 2 Menu has similar content as Input 1 menu. The settings are applied to input 2.
OUTPUT Menu
Heading of OUTPUT menu. Press Enter to enter submenu content.
Output Relay 1
Heading of output relay 1 menu. Press Enter to enter submenu content.
Rst Trip/Alarm
Yes
Set to yes to enable the input to reset trip and alarm.
Rst Thermal
θ
%
Yes
Set to yes to enable the input to reset thermal %.
Aux timer
500ms
Relay 1 Func Trip
Set the function of output Relay 1. Note that Relay 1 function is
locked to Trip.
Reset
Auto
Set the reset method of relay: Auto (Unlatched), Manual (Latched).
tI>?
Yes
Assign I> trip to the output relay.
tI>>?
Yes
Assign I>> trip to the output relay.
7.OUTPUT