46
Negative sequence
overcurrent,
0.1 to 40 x In
Is ± 5% or 30mA
whichever greater
0.95 x Is ± 3%
DT: ±2% +30ms
I2>
IDMT: ±6% +30ms
(>1.2 x Is)
Thermal overload, I
θ
>
0.1 to 3 x In
±5%
INSULATION
High voltage dielectric withstand test IEC60255-5
: 2kV rms, 1 minute
High voltage impulse test IEC60255-5
: 5kV, 1.2/50us
STANDARDS
Complies with IEC 60255-26 standard
Electrical fast transient IEC61000-4-4, power supply
: 4kV, 5kHz
Electrical fast transient IEC61000-4-4, other inputs
: 2kV, 5kHz
Surge IEC61000-4-5, IEC 60255-22-5
: 4kV common mode
: 2kV differential mode
Electrostatic discharge IEC61000-4-2, air discharge
: 8 kV
Electrostatic discharge IEC61000-4-2, contact discharge : 6 kV
1MHz burst disturbance IEC60255-22-1
: 2kV Common mode
: 1kV Differential mode
Conducted Immunity IEC61000-4-6
: 10V rms @ 1kHz 80%AM, 0.15 to 80MHz
Radiated Immunity IEC61000-4-3
: 10V/m 80Mhz to 1GHz @1kHz 80% am
Conducted emissions
: EN 55011 Group 1 Class B
Radiated EM Field emission
: CISPR 11 Group 1 Class B
ENVIRONMENTAL CONDITIONS
Temperature
: -5ºC to 55ºC
Humidity
: 56 days at 93% RH and 40ºC non-condensing
MECHANICAL
Mounting
: Panel mounting
Dimension (mm)
: 142(w) x 165(h) x 198(d)
Enclosure protection
: IP54 at the panel
Approximate weight
: 3kg