28
Displays the summation of the current (in Amps or square Amps, set
by ‘n’ in CB Alarm menu) for phase 1 interrupted by the circuit
breaker.
Same as above for phase 2
Same as above for phase 3
Reset all the counter value in CB Monitor menu,
CB Alarm
Heading of CB Alarm menu. Press Enter to enter submenu content.
Set to Yes to enable circuit breaker opening alarm. The following
menu is displayed.
Set the value for the circuit breaker opening time threshold.
Set to Yes to enable circuit breaker closing alarm. The following menu
is displayed.
Set the value for the circuit breaker closing time threshold.
Set to Yes to enable circuit breaker operations alarm. The following
menu is displayed.
Set the value for the circuit breaker operations threshold.
Set to Yes to enable the summation of the current (in Amps or square
Amps) alarm.
9.2 CB Alarm
Σ
Amps(n) IL1
345 kA
Σ
Amps(n) IL2
12 kA
Σ
Amps(n) IL3
1.2 MA
Reset All Value
RST=CLEAR
CB Opening Time?
Yes
CB Opening Time
150ms
CB Closing Time?
Yes
CB Closing Time
250ms
CB Operations?
Yes
CB Operations
200
ΣAmps(n)?
Yes