57
CODE
DESCRIPTION
F1
2 bytes ASCII character
F2
Unsigned integer – Relay status
Bit 0: Eeprom data failure
Bit 11: Back port (RS485) unread fault record
Bit 1: Calibration failure
Bit 12: Front panel (RS232) unread fault record
Bit 2: Clock loss
Bit 13: Front panel/Back port communication
Bit 3: Clock error
Bit 14: Back port unread alarm record
Bit 4: Adc error
Bit 15: Front panel unread alarm record
F3
Unsigned integer – Relay LED status
Bit 0 and Bit 1: Trip LED. 1=on, 2=blink
Bit 5: LED2 1=on, 0=off
Bit 2 and Bit 3: Alarm LED. 1=on, 2=blink
Bit 6: LED3 1=on, 0=off
Bit 4: LED1 1=on, 0=off
Bit 7: LED4 1=on, 0=off
F4
Unsigned integer – Input status
Bit 0: Input 1 (0=off, 1=on)
Bit 1: Input 2 (0=off, 1=on)
F5
Unsigned integer – Output relay status
Bit 0: Output 1 (0=off, 1=on)
Bit 1: Output 2 (0=off, 1=on)
Bit 2: Output 3 (0=off, 1=on)
Bit 3: Output 4 (0=off, 1=on)
F6
Unsigned integer – Miscellaneous
A numeric value representation of certain options or functions.
Refer to 'range' column of the register for detail.
F7
Unsigned integer
A numeric value of certain units
Eg. 12 may represent 12% or 12minutes
Refer to individual resisger's 'Units and 'range' for detail
F8
Unsigned long integer – A numeric value of certain units
F9
Unsigned integer – Remote command
High byte:
1: Reset alarm/trip (also acknowledge and
7: Reset panel password
delete alarm record)
8: Delete fault record
2: Acknowledge alarm/trip
9: Delete event record
3: Reset display to main page
10: Delete alarm record
4: Reset thermal state
11: Start Disturbance Record
5: Reset maximum and average
12: Remote CB close
measurement value
13: Reset CB Monitor value
6: Remote trip
Low byte:
For high byte=3: set to main display page 0-3
For hight byte=8,9 and 10: 0=Delete all record, n: delete record n
F10
Unsigned integer
High byte: month
Low byte: day
F11
Unsigned integer
High byte: hour (24 hour format)
Low byte: minute
F12
Unsigned integer – Date and time format for relay display only
High byte: Date format, 0=DD/MM/YYYY, 1=MM/DD/YYYY
Low byte: Time format, 0=12 hour, 1=24 hour
F13
Unsigned integer – Change Group by...
0=Change group by menu, 1=change group change by level of digital
input
9.3 MODBUS Mapping Format