19
Io> menu
Set to Yes to enable earth fault first threshold (Io>). Then the
following menu is displayed.
Set the value for the current threshold Io>.
NOTE : When delay type is IDMT, the maximum setting
recommended should be 0.5Ion..
Set the time delay type of Io>. Setting choices are: IDMT and Definite
Time.
If Definite Time is selected, the following menu is displayed:
Set the value for the time delay of Io> definite time.
If IDMT is selected, the following menu is displayed:
Set the type of curve.
Set the time multiplier setting value for the curve.
Io>> menu
Set to Yes to earth fault second threshold (Io>>). Then the following
menu is displayed.
Set the value for the current threshold Io>>.
Set the value for the time delay of Io>> definite time.
Io>>> menu
Set to Yes to enable earth fault third threshold (Io>>>). Then the
following menu is displayed.
Set to yes to enable Io>>> operated on current sample base. Otherwise
it operates on fundamental value.
Sample base method will
ensure fast
tripping on highly saturated current signal.
Io>?
Yes
Io>
0.10Ion
Io> Delay Type
IDMT
tIo>
1.00s
Io> IDMT Curve
Normal Invrse
ktIo>
0.20
Io>>?
Yes
Io>>
1.00Ion
tIo>>
100ms
Io>>>?
Yes
Io>>> Sample
Yes