17
Io>>?
Yes
Assigned Io>> start to LED
tIo>>?
Yes
Assigned tIo>> trip to LED
Io>>>?
Yes
Assigned Io>>> start to LED
tIo>>>?
Yes
Assigned tIo>>> trip to LED
tI2>?
Yes
Assigned I2> start to LED
tI2>>?
Yes
Assigned tI2> trip to LED
Input 1?
Yes
Assigned Input 1 status to LED
Input 2?
Yes
Assigned Input 2 status to LED
Aux 1?
Yes
Assigned Aux1 Alarm/trip to LED
Aux 2?
Yes
Assigned Aux2 Alarm/trip to LED
Thml Alrm?
Yes
Assigned thermal alarm to LED
Thml Trip?
Yes
Assigned thermal trip to LED
CB Fail?
Yes
Assigned CB fail to LED
Reclsr Run?
Yes
Assigned recloser running to LED
Reclsr Lockd? Yes
Assigned recloser locked to LED
TCS Alrm?
Yes
Assigned TCS alarm to LED
PROTECTION G1 Menu
Heading of PROTECTION G1 (Group 1) menu. Press Enter to enter
submenu content.
Phase OC Menu
Heading of Phase OC (Overcurrent) menu. Press Enter to enter
submenu content.
I> menu
Set to Yes to enable phase overcurrent first threshold (I>). Then the
following menu is displayed.
Set the value for the current threshold I>.
NOTE : When delay type is IDMT, the maximum setting
recommended should be 2.00In.
Set the time delay type of I>. Setting choices are: IDMT (inverse
definite time curve) and Definite Time.
4.PROTECTION G1
4.1 Phase OC
I>?
Yes
I>
2.00In
I> Delay Type
IDMT