capaNCDT 6500
Page 40
Ethernet Interface
6.4.11 Get Linearization Point (GLP)
Reads out the linearization point.
The value is output as a 6-digit number in hex format (000000 to FFFFFF).
GLP
Command
$GLPm:n<CR> (for example: $GLP5:3<CR> = linearization point at
30 % of channel 5)
Response
$GLPm:n,……OK<CRLF> (zum Beispiel $GLP5:3,A034C9OK<CRLF>)
Index
m (Channel number): 1…8
n (linearization point):
1 = linearization point at 10 % of the measuring range
2 = linearization point at 20 % of the measuring range
3 = linearization point at 30 % of the measuring range
4 = linearization point at 40 % of the measuring range
5 = linearization point at 50 % of the measuring range
6 = linearization point at 60 % of the measuring range
7 = linearization point at 70 % of the measuring range
8 = linearization point at 80 % of the measuring range
9 = linearization point at 90 % of the measuring range
10 = linearization point at 100 % of the measuring range
6.4.12 Status (STS)
Reads all settings at once.
The individual parameters are separated by a semicolon. The structure of the respective
responses corresponds to those of the individual requests.
STS
Command
$STS<CR>
Response
$STSSRAn;AVTn;AVNn;CHS…;CHT…;TRG.;LINn,n,n,n,n,n,n,n;DISa,bOK
<CRLF>
6.4.13 Version (VER)
Requesting the current software version including date.
VER
Command
$VER<CR>
Response
$VERDT6500;V1.2a;8010074<CRLF>
6.4.14 Display Setups (DIS)
Defines
-
which values are shown on the display (linearized or non-linearized values)
-
which channels are updated on the display.
DIS
Command
$DISa,b<CR>
Response
$DISa,bOK<CRLF>
Index
a (Display update):
1 = All channels are updated (Default setting)
2 = Only the channels to be transmitted are updated
0 = No channels are updated
b (Display values):
0 = Non-linearized measuring values are displayed (Default setting)
1 = Linearized measuring values are indicated
Request display settings
Command
$DIS?<CR>
Response
$DIS?a,bOK<CRLF>