KE600 Inverter Parameter Description
83
P1-30
Phase-sequence of ABZ
incremental encoder
Factory default
0
Setting range
0: forward
1: reverse
To set the phase-sequence of encoder A, B signal
P1-36
Detection time of PG cables
disconnection
Factory default
0.0
Setting range
0.0: no detection
0.1~10.00s
To set the detection time of encoder cables disconnection, if the set time is 0.0s, the inverter will not detect
whether the encoder cable is disconnected or not.
While the encoder cables disconnect, and the time of duration is more than P1-36, the inverter will give
failure information of “E-20”.