KE600 Inverter Function Parameter List
59
Function
code
Name
Detailed instruction
Factory
default
Modify
Thousands place: Motor over heat (25)
Ten thousands: Running time arrival
(26)
P9-49
Fault protection action
selection 3
Units place: Customized fault 1 (27)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Tens place: Customized fault 2 (28)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Hundreds place: Power-on time arrival
time (29)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Thousands place: Off load (30)
0: Coast to stop
1: Dec-to-stop
2: Decelerate to 7% of motor rated
power, then keep running; run at
setting frequency when no off-load
Ten thousands place: PID feedback
lost when running (31)
0: Coast to stop
1: Dec-to-stop
2: Keep running
00000
○
P9-50
Fault protection action
selection 4
Units place:
Speed deviation oversize (42)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Tens place: motor over speed (43)
Hundreds place: Initial place fault (51)
00000
○
P9-54
Running frequency
selection when fault
0: Run at current running frequency
1: Run at setting frequency
2: Run at upper limit frequency
3: Run at lower limit frequency
4: Run at abnormal backup frequency
0
○
P9-55
Abnormal backup
frequency
60.0% ~ 100.0% (100.0% corresponds
to maximum frequency( P0-10))
100.0%
○
P9-56
~
Reserved
●