![Micno KE600 Series Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/micno/ke600-series/ke600-series_manual_1784752046.webp)
KE600 Inverter Function Parameter List
43
Function
code
Name
Detailed instruction
Factory
default
Modify
reference frequency
1: Setting frequency
2: 100Hz
P0-26
Running frequency
command UP/DN
reference
0: Running frequency
1: Setting frequency
0
◎
P1 Group: Motor 1 Parameters
P1-00
Motor type
0: Common asynchronous motor
1: Variable frequency asynchronous
motor
0
◎
P1-01
Rated power
0.1kW ~ 1000.0kW
Model
depend
◎
P1-02
Rated voltage
1V ~ 2000V
Model
depend
◎
P1-03
Rated current
0.01A ~ 655.35A
( Inverter power≤55kW )
0.1A ~ 6553.5A
( Inverter power
>
55kW )
Model
depend
◎
P1-04
Rated frequency
0.00Hz ~ P0-10 (max. frequency)
Model
depend
◎
P1-05
Rated speed
1rpm ~ 36000rpm
Model
depend
◎
P1-06
Stator resistance
0.001
Ω ~ 65.535Ω
( Inverter power≤55kW)
0.0001Ω ~ 6.5535Ω
( Inverter power
>
55kW)
Motor
paramet
er
◎
P1-07
Rotor resistance
0.001
Ω ~ 65.535Ω
( Inverter power≤55kW)
0.0001Ω ~ 6.5535Ω
( Inverter power
>
55kW)
Motor
paramet
er
◎
P1-08
Leakage inductance
0.01mH ~ 655.35mH
( Inverter power≤55kW)
0.001mH ~ 65.535mH
( Inverter power
>
55kW)
Motor
paramet
er
◎
P1-09
Mutual inductance
0.01mH ~ 655.35mH
( Inverter power≤55kW)
0.001mH ~ 65.535mH
( Inverter power
>
55kW)
Motor
paramet
er
◎
P1-10
No-load current
0.01A ~ P1-03 (rated current)
( Inverter power≤55kW)
0.1A ~ P1-03 (rated current)
( Inverter power
>
55kW)
Motor
paramet
er
◎