KE600 Inverter Parameter Description
79
P0-24
Motor parameters selection
Factory default
0
Setting range
0
Motor 1
1
Motor 2
KE600 is compatible with 2 motors driving in different time, two motors can be set different parameters
(motor nameplate) separately, these two motors can perform autotuning, select different control mode and
set different operation parameters individually. Parameters P1 and P2 group is special for motor1, A2
group is for motor2, customers can select motor1 or motor2 by P0-24.
P0-25
ACC/DEC time reference frequency
Factory default
0
Setting range
0
P0-10 (maximum frequency)
1
Setting frequency
2
100Hz
ACC/DEC time is ACC/DEC time from 0Hz to the frequency set by P0-25, figure 6-1 is ACC/DEC time
schematic diagram.
When P0-25 is set to 1, ACC/DEC time is related to setting frequency. The motor acceleration will change if
setting frequency changes frequently.
P0-26
Running frequency command
UP/DN reference
Factory default
0
Setting range
0
Running frequency
1
Setting frequency
This parameter is only valid when frequency source is set by keypad.
It is used to confirm which mode would be used to modify setting frequency when keys “▲”, “▼” or terminal
UP, DOWN acts, namely, whether reference frequency increases/decreases on the basic of running
frequency, or increases/decreases on the basic of setting frequency.