KE600 Inverter Parameter Description
152
Group A2 Motor 2 Parameters
A2-00
Motor type
Factory default
0
Setting range
0
Common asynchronous motor
1
Variable frequency asynchronous motor
A2-01
Motor rated power
Factory default
Model depend
Setting range
0.1kW ~ 1000.0kW
A2-02
Motor rated voltage
Factory default
Model depend
Setting range
1V ~ 2000V
A2-03
Motor rated current
Factory default
Model depend
Setting range
0.01A ~ 655.35A
(Inverter power≤55kW)
0.1A ~ 6553.5A (Inverter power
>
55kW)
A2-04
Motor rated frequency
Factory default
Model depend
Setting range
0.01Hz ~ P0-10 (maximum frequency)
A2-05
Motor rated speed
Factory default
Model depend
Setting range
1RPM ~ 65535RPM
1. Please set the parameters correctly according to the motor nameplate.
2. In order to achieve superior control performance, please perform motor parameters autotuning. The
accuracy of autotuning is closely related to the correct setting of the rated motor parameters.
A2-06
Motor stator resistance
Factory default
Model depend
Setting range
0.001
Ω ~ 65.535Ω (Inverter power≤55kW)
0.0001Ω ~ 6.5535Ω (Inverter power
>
55kW)
A2-07
Motor rotor resistance
Factory default
Model depend
Setting range
0.001Ω ~ 65.535Ω (Inverter power≤55kW)
0.0001Ω ~ 6.5535Ω (Inverter power
>
55kW)
A2-08
Motor leakage inductive
Factory default
Model depend
Setting range
0.01mH ~ 655.35mH
(Inverter power≤55kW)
0.001mH ~ 65.535mH (Inverter power
>
55kW)
A2-09
Motor mutual inductive
Factory default
Model depend
Setting range
0.1mH ~ 6553.5mH
(Inverter power≤55kW)
0.01mH ~ 655.35mH (Inverter power
>
55kW)
A2-10
Motor current without load
Factory default
Model depend
Setting range
0.01A ~ P1-03
(Inverter power≤55kW)
0.1A ~ P1-03 (Inverter power
>
55kW)
A2-06 ~ A2-10 are motor parameters, which cannot be found on the motor nameplate, the values are
obtained via the inverter autotuning. The static autotuning only can obtain A2-06 ~ A2-08. The rotation
autotuning not only can obtain A2-06 ~ A2-10, but also can get current loop PI parameter, etc.
When A2-01 or A2-02 changed, the values of A2-06 ~ A2-10 will be changed automatically, and restore