KE600 Inverter Mechanical and Electric Installation
25
Inverter Model
Circuit Breaker
(MCCB)
A
Recommended
Contactor
A
Recommended
Conducting
Wire of Main
Circuit at Input
Side
mm
2
Recommended
Conducting
Wire of Main
Circuit at
Output Side
mm
2
Recommended
Conducting
Wire of Control
Circuit
mm
2
3AC 380~440V
KE600-1R5G-T4
16
10
2.5
2.5
1.0
KE600-2R2G-T4
16
10
2.5
2.5
1.0
KE600-004G-T4
25
16
4.0
4.0
1.0
KE600-5R5G-T4
32
25
4.0
4.0
1.0
KE600-7R5G-T4
40
32
4.0
4.0
1.0
KE600-011G-T4
63
40
4.0
4.0
1.0
KE600-015G-T4
63
40
6.0
6.0
1.0
KE600-018G-T4
100
63
6.0
6.0
1.5
KE600-022G-T4
100
63
10
10
1.5
KE600-030G-T4
125
100
16
10
1.5
KE600-037G-T4
160
100
16
16
1.5
KE600-045G-T4
200
125
25
25
1.5
KE600-055G-T4
200
125
35
25
1.5
KE600-075G-T4
250
160
50
35
1.5
KE600-090G-T4
250
160
70
35
1.5
KE600-110G-T4
350
350
120
120
1.5
KE600-132G-T4
400
400
150
150
1.5
KE600-160G-T4
500
400
185
185
1.5
KE600-200G-T4
600
600
150*2
150*2
1.5
KE600-220G-T4
600
600
150*2
150*2
1.5
KE600-250G-T4
800
600
185*2
185*2
1.5
KE600-280G-T4
800
800
185*2
185*2
1.5
KE600-315G-T4
800
800
150*3
150*3
1.5
KE600-350G-T4
800
800
150*4
150*4
1.5
KE600-400G-T4
1000
1000
150*4
150*4
1.5
KE600-500G-T4
1200
1200
180*4
180*4
1.5
KE600-560G-T4
1200
1200
180*4
180*4
1.5
KE600-630G-T4
1500
1500
180*4
180*4
1.5