KE600 Inverter Parameter Description
101
Group P5 Output Terminal
The standard Inverter has 2 multifunctional analog output terminals, 2 multifunctional relay output terminals,
1 HDO terminal (can be used as either high-speed pulse output terminal or collector open output).
P5-00
HDO terminal output selection
Factory default
0
Setting range
0
High speed pulse output
1
Open collector output
HDO terminal is programmable multiplexing terminal, can be used as high-speed pulse output, with
maximum frequency 100.00 kHz. Refer to P5-06 for details.
P5-01
HDO open collector output selection
Factory default
0
P5-02
Relay 1 output function selection
Factory default
2
P5-03
Relay 2 output function selection
Factory default
0
P5-04
Y1 output selection
Factory default
0
P5-05
Y2 output selection
Factory default
0
The parameters are used to select the functions of 3 digital outputs.
Multifunctional output terminal function selection is as follows:
Note:
1: Relay2, Y1 and Y2 are from the I/O extension card
2: Y1 and Y2 are open collector type output terminals.
Setting
value
Function
Description
0
No output
The output terminals do not have any functions.
1
Inverter is running
It indicates the inverter is running, and there is output frequency
(can be zero), and the inverter outputs ON signal at this time.
2
Fault output (fault stop)
When the inverter is faulty & it stops, it outputs ON signal.
3
FDT1 output
Please refer to P8-19 and P8-20 for details.
4
Frequency arrival
Please refer to P8-21 for details.
5
Zero speed running (no
output when stop)
When the inverter is running & the output frequency is 0, it
outputs ON signal. When the inverter stopped, the signal is
OFF.
6
Motor overload
pre-alarm
Judgment will be made according to the pre-warning threshold
value before the motor overload protection action. If it exceeds
the pre-warning threshold, it will output ON signal. Motor
overload parameters are set in P9-00 to P9-02.
7
Inverter overload pre-
alarm
The inverter outputs ON signal 10s before overload protection
action
8
Setting count value
arrival
When the counting value reaches the setting value of PB-08, it
outputs ON signal.
9
Designated count value
arrival
When the counting value reaches the setting value of PB-09, it
outputs ON signal. Refer to Group B function description for the
counting function.
10
Length arrival
When the measured actual length exceeds the setting value of