KE600 Inverter Mechanical and Electric Installation
34
Figure 3-12 NPN type wiring
This is the most commonly used wiring connection, if external power supply is used, the +24V terminal
must disconnect with PLC terminal. The positive pole of external power supply should connect with PLC
terminal, and the negative pole connects with COM.
D1~D10 (D8~D10 on the I/O extension card) terminals connection:
PNP type
Figure 3-13 PNP type wiring
In this type, +24V terminal must disconnect with PLC terminal, +24V should connect the common port of
external controller, and meantime short connect PLC and COM.
External controller
NPN
3.3
Ω
0V
CO
M
+VCC
Signal
+24
V
+24
V
D
5
3.3
K
3.3K
D
1
PLC
Control board of inverter
External controller
PNP
COM
+VCC
+24V
+24V
D5
4.7K
4.7K
D1
Control board of inverter
0V
Signal
3.3
Ω
PLC